Public water system record

Glenwood Water Works

Serves Glenwood, Rush County, IN · 313 people served

Federal records show 15 health-based violations and 2 monitoring/reporting issues for Glenwood Water Works in the last ten years. The most serious issue in this window was a Total Trihalomethanes (TTHMs) violation that EPA lists as archived, not resolved.

  • IN5270002
  • GLENWOOD
  • IN
  • 313 served

System profile

Source water Groundwater
ZIP 46133
EPA system ID IN5270002

Verify this system on EPA ECHO →

Health-based violations, last 10 years
15
Resolved
8
Unresolved
0
Archived by EPA
7
Any acute record
No
Monitoring issues, last 10 years
2

Key facts

  • Glenwood Water Works draws water from 2 wells.
  • Highest measured level in the last 10 years: Total Trihalomethanes (TTHMs), 142 µg/L, federal limit 80 µg/L (1.8 times the limit), 2025.
  • Most recent formal enforcement: compliance order with a penalty by Indiana, August 2017.
  • Record on file since 1980, with 14 health-based violations before October 19, 2016.
  • Lead pipe inventory: 0 lead and 0 unknown out of 160 service lines.

Check whether Glenwood Water Works serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

Contaminant Rule family Start date Status Acute
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 137 µg/L, federal limit 80 µg/L (1.7 times the limit)
220 Oct 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 82.8 µg/L, federal limit 60 µg/L (1.4 times the limit)
220 Jul 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 141 µg/L, federal limit 80 µg/L (1.8 times the limit)
220 Jul 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 96.6 µg/L, federal limit 60 µg/L (1.6 times the limit)
220 Apr 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 142 µg/L, federal limit 80 µg/L (1.8 times the limit)
220 Apr 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 108.9 µg/L, federal limit 80 µg/L (1.4 times the limit)
220 Jan 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 102.7 µg/L, federal limit 60 µg/L (1.7 times the limit)
220 Jan 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 82.5 µg/L, federal limit 80 µg/L (at or just above the limit)
220 Oct 1, 2018 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 83.9 µg/L, federal limit 80 µg/L (at or just above the limit)
220 Jul 1, 2018 Resolved No
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 60.9 µg/L, federal limit 60 µg/L (at or just above the limit)
220 Apr 1, 2017 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 86 µg/L, federal limit 80 µg/L (1.1 times the limit)
220 Apr 1, 2017 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 93.2 µg/L, federal limit 80 µg/L (1.2 times the limit)
220 Jan 1, 2017 Resolved No
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 65.7 µg/L, federal limit 60 µg/L (1.1 times the limit)
220 Jan 1, 2017 Resolved No
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 64.5 µg/L, federal limit 60 µg/L (1.1 times the limit)
220 Oct 1, 2016 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 90.8 µg/L, federal limit 80 µg/L (1.1 times the limit)
220 Oct 1, 2016 Resolved No

Monitoring and reporting issues

Since October 2016

Missed tests or reports, not contaminants found above a limit.

Issue Start date Status
Groundwater Rule
OTHER
Sep 12, 2023 Active
Revised Total Coliform Rule
RPT
Aug 1, 2021 Resolved

Full record since 1980

EPA's records for Glenwood Water Works go back to 1980. Before October 19, 2016 they list 14 health-based violations (14 resolved) and 3 monitoring or reporting violations.

Violations that began in Health-based Monitoring and reporting
1980s 0 1
1990s 0 2
2000s 1 0
2010 to October 18, 2016 13 0
October 19, 2016 to 2019 6 0
2020s 7 2

Most recent health-based violation before October 19, 2016: Haloacetic Acids (HAA5), began October 2016, Resolved.

Show all 14 health-based violations before October 19, 2016
Contaminant Start date Status
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 64.5 µg/L, federal limit 60 µg/L (1.1 times the limit)
Oct 1, 2016 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 90.8 µg/L, federal limit 80 µg/L (1.1 times the limit)
Oct 1, 2016 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 71.2 µg/L, federal limit 60 µg/L (1.2 times the limit)
Jul 1, 2016 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 89.3 µg/L, federal limit 80 µg/L (1.1 times the limit)
Jul 1, 2016 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 74.3 µg/L, federal limit 60 µg/L (1.2 times the limit)
Apr 1, 2016 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 87.2 µg/L, federal limit 80 µg/L (1.1 times the limit)
Apr 1, 2016 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.094 mg/L, federal limit 0.06 mg/L (1.6 times the limit)
Apr 1, 2012 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.09 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
Apr 1, 2012 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.093 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
Jan 1, 2012 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 0.061 mg/L, federal limit 0.06 mg/L (at or just above the limit)
Jan 1, 2012 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.085 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
Oct 1, 2011 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.082 mg/L, federal limit 0.08 mg/L (at or just above the limit)
Jul 1, 2011 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.084 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
Apr 1, 2011 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Apr 1, 2005 Resolved

Enforcement actions

Indiana regulators took 1 formal enforcement action against Glenwood Water Works in 2017. The most recent was a compliance order with a penalty in August 2017.

Date By Action Violations covered
Aug 28, 2017 Indiana Compliance order with a penalty 6 violations (6 health-based): Haloacetic Acids (HAA5), Total Trihalomethanes (TTHMs)

What the violations mean

Total Trihalomethanes (TTHMs)

9 incidents

Disinfection byproduct levels exceeded the federal limit

Long-term TTHM exposure may increase bladder cancer risk

Haloacetic Acids (HAA5)

6 incidents

Haloacetic acid byproducts exceeded the federal limit

Long-term exposure to HAAs may increase cancer risk

Where the water comes from

Glenwood Water Works draws water from 2 wells.

Annual water quality report

Glenwood Water Works must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Systems serving 500 or fewer people may meet the rule by telling customers the report is available on request, so you may need to ask Glenwood Water Works for a copy.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water

To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Indiana.