Public water system record

Standard

Serves Standard, Putnam County, IL · 203 people served

Federal records show no health-based violations and no monitoring or reporting issues for Standard in the last ten years.

  • IL1550300
  • STANDARD
  • IL
  • 203 served

System profile

Source water Groundwater
ZIP 61363
EPA system ID IL1550300

Verify this system on EPA ECHO →

Health-based violations, last 10 years
0
Resolved
0
Unresolved
0
Any acute record
No
Monitoring issues, last 10 years
0

Key facts

  • Standard draws water from 2 wells (1 of them for emergency, seasonal or other part-time use).
  • Most recent formal enforcement: signed compliance agreement by Illinois, October 2007.
  • Record on file since 1977, with 43 health-based violations before October 19, 2016.
  • Lead pipe inventory: 10 lead and 29 unknown out of 126 service lines.

Check whether Standard serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

None since October 2016, and no monitoring or reporting violations either.

Full record since 1977

EPA's records for Standard go back to 1977. Before October 19, 2016 they list 43 health-based violations (40 resolved, 3 archived by EPA without a recorded fix) and 123 monitoring or reporting violations.

Violations that began in Health-based Monitoring and reporting
1970s 0 1
1990s 5 31
2000s 34 88
2010 to October 18, 2016 4 3

Most recent health-based violation before October 19, 2016: Arsenic, began October 2013, Resolved.

Show all 43 health-based violations before October 19, 2016
Contaminant Start date Status
Arsenic
Contaminant limit exceeded
Measured 0.011 mg/L, federal limit 0.01 mg/L (1.1 times the limit)
Oct 1, 2013 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.014 mg/L, federal limit 0.01 mg/L (1.4 times the limit)
Jul 1, 2013 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.017 mg/L, federal limit 0.01 mg/L (1.7 times the limit)
Apr 1, 2013 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.029 mg/L, federal limit 0.01 mg/L (2.9 times the limit)
Jan 1, 2013 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 8 pCi/L, federal limit 5 pCi/L (1.6 times the limit)
Jul 1, 2007 Resolved
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 19 pCi/L, federal limit 15 pCi/L (1.3 times the limit)
Apr 1, 2007 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 10 pCi/L, federal limit 5 pCi/L (2 times the limit)
Apr 1, 2007 Resolved
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 19 pCi/L, federal limit 15 pCi/L (1.3 times the limit)
Jan 1, 2007 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 12 pCi/L, federal limit 5 pCi/L (2.4 times the limit)
Jan 1, 2007 Resolved
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 20 pCi/L, federal limit 15 pCi/L (1.3 times the limit)
Oct 1, 2006 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 12 pCi/L, federal limit 5 pCi/L (2.4 times the limit)
Oct 1, 2006 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 12 pCi/L, federal limit 5 pCi/L (2.4 times the limit)
Jul 1, 2006 Resolved
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 18 pCi/L, federal limit 15 pCi/L (1.2 times the limit)
Jul 1, 2006 Resolved
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 16 pCi/L, federal limit 15 pCi/L (1.1 times the limit)
Apr 1, 2006 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 14 pCi/L, federal limit 5 pCi/L (2.8 times the limit)
Apr 1, 2006 Resolved
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 16 pCi/L, federal limit 15 pCi/L (1.1 times the limit)
Jan 1, 2006 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 12 pCi/L, federal limit 5 pCi/L (2.4 times the limit)
Jan 1, 2006 Resolved
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 16 pCi/L, federal limit 15 pCi/L (1.1 times the limit)
Oct 1, 2005 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Oct 1, 2005 Resolved
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 16 pCi/L, federal limit 15 pCi/L (1.1 times the limit)
Jul 1, 2005 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Jul 1, 2005 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Apr 1, 2005 Resolved
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 38.6 pCi/L, federal limit 15 pCi/L (2.6 times the limit)
Apr 1, 2005 Resolved
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Jan 1, 2005 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Jan 1, 2005 Resolved
DICHLOROMETHANE
Contaminant limit exceeded
Oct 1, 2004 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Oct 1, 2004 Resolved
DICHLOROMETHANE
Contaminant limit exceeded
Jul 1, 2004 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Jul 1, 2004 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Apr 1, 2004 Resolved
DICHLOROMETHANE
Contaminant limit exceeded
Apr 1, 2004 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Jan 1, 2004 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Oct 1, 2003 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Jul 1, 2003 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Apr 1, 2003 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Jan 1, 2003 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Oct 1, 2002 Resolved
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Jan 1, 2002 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Aug 1, 1999 Archived
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Jan 1, 1998 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Aug 1, 1995 Archived
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Dec 30, 1993 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Aug 1, 1991 Archived

Enforcement actions

Illinois regulators took 5 formal enforcement actions against Standard and issued 1 ban on new connections between 1991 and 2007. The most recent was a signed compliance agreement in October 2007.

Date By Action Violations covered
Oct 31, 2007 Illinois Signed compliance agreement 3 violations (3 health-based): Gross Alpha, Excl. Radon and U, Combined Radium (-226 and -228)
Nov 24, 2004 Illinois Signed compliance agreement 3 violations (3 health-based): DICHLOROMETHANE
Oct 6, 2004 Illinois Signed compliance agreement 8 violations: Public Notice
Feb 26, 2004 Illinois Signed compliance agreement 33 violations (33 health-based): Gross Alpha, Excl. Radon and U, Combined Radium (-226 and -228)
Nov 26, 2001 Illinois Signed compliance agreement 8 violations (8 health-based): Combined Radium (-226 and -228), Gross Alpha, Excl. Radon and U
Sep 16, 1991 Illinois Ban on new connections or service extensions 1 violation (1 health-based): Combined Radium (-226 and -228)

Where the water comes from

Standard draws water from 2 wells (1 of them for emergency, seasonal or other part-time use).

Annual water quality report

Standard must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Systems serving 500 or fewer people may meet the rule by telling customers the report is available on request, so you may need to ask Standard for a copy.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water

To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Illinois.