Public water system record

Dixon

Serves Dixon, Lee County, IL · 15,096 people served

Federal records show no health-based violations and 2 monitoring/reporting issues for Dixon in the last ten years. At least one of these issues remains unresolved.

  • IL1030200
  • DIXON
  • IL
  • 15,096 served

System profile

Source water Groundwater
ZIP 61021
EPA system ID IL1030200

Verify this system on EPA ECHO →

Health-based violations, last 10 years
0
Resolved
0
Unresolved
0
Any acute record
No
Monitoring issues, last 10 years
2

Key facts

  • Dixon draws water from 7 wells.
  • Most recent formal enforcement: signed compliance agreement by Illinois, January 2009.
  • Record on file since 1977, with 40 health-based violations before October 19, 2016.

Check whether Dixon serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

None since October 2016.

Monitoring and reporting issues

Since October 2016

Missed tests or reports, not contaminants found above a limit.

Issue Start date Status
Lead and Copper Rule
Monitoring and reporting
Jul 1, 2025 Active
Combined Radium (-226 and -228)
Monitoring and reporting
Apr 1, 2022 Resolved

Full record since 1977

EPA's records for Dixon go back to 1977. Before October 19, 2016 they list 40 health-based violations (40 resolved) and 2 monitoring or reporting violations.

Violations that began in Health-based Monitoring and reporting
1970s 0 1
2000s 40 1
2020s 0 2

Most recent health-based violation before October 19, 2016: Arsenic, began July 2009, Resolved.

Show all 40 health-based violations before October 19, 2016
Contaminant Start date Status
Arsenic
Contaminant limit exceeded
Measured 0.012 mg/L, federal limit 0.01 mg/L (1.2 times the limit)
Jul 1, 2009 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 6 pCi/L, federal limit 5 pCi/L (1.2 times the limit)
Apr 1, 2009 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.012 mg/L, federal limit 0.01 mg/L (1.2 times the limit)
Apr 1, 2009 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 8 pCi/L, federal limit 5 pCi/L (1.6 times the limit)
Jan 1, 2009 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.012 mg/L, federal limit 0.01 mg/L (1.2 times the limit)
Jan 1, 2009 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 7 pCi/L, federal limit 5 pCi/L (1.4 times the limit)
Oct 1, 2008 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.011 mg/L, federal limit 0.01 mg/L (1.1 times the limit)
Oct 1, 2008 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.011 mg/L, federal limit 0.01 mg/L (1.1 times the limit)
Jul 1, 2008 Resolved
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 16 pCi/L, federal limit 15 pCi/L (1.1 times the limit)
Jul 1, 2008 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 7 pCi/L, federal limit 5 pCi/L (1.4 times the limit)
Jul 1, 2008 Resolved
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 16 pCi/L, federal limit 15 pCi/L (1.1 times the limit)
Apr 1, 2008 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 7 pCi/L, federal limit 5 pCi/L (1.4 times the limit)
Apr 1, 2008 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 7 pCi/L, federal limit 5 pCi/L (1.4 times the limit)
Jan 1, 2008 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 7 pCi/L, federal limit 5 pCi/L (1.4 times the limit)
Oct 1, 2007 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 8 pCi/L, federal limit 5 pCi/L (1.6 times the limit)
Jul 1, 2007 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 8 pCi/L, federal limit 5 pCi/L (1.6 times the limit)
Apr 1, 2007 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 8 pCi/L, federal limit 5 pCi/L (1.6 times the limit)
Jan 1, 2007 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 7 pCi/L, federal limit 5 pCi/L (1.4 times the limit)
Oct 1, 2006 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 8 pCi/L, federal limit 5 pCi/L (1.6 times the limit)
Jul 1, 2006 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 7 pCi/L, federal limit 5 pCi/L (1.4 times the limit)
Apr 1, 2006 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 7 pCi/L, federal limit 5 pCi/L (1.4 times the limit)
Jan 1, 2006 Resolved
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 16 pCi/L, federal limit 15 pCi/L (1.1 times the limit)
Jan 1, 2006 Resolved
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Oct 1, 2005 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Oct 1, 2005 Resolved
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Jul 1, 2005 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Jul 1, 2005 Resolved
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Apr 1, 2005 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Apr 1, 2005 Resolved
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Jan 1, 2005 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Jan 1, 2005 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Oct 1, 2004 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Jul 1, 2004 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Apr 1, 2004 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Jan 1, 2004 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Oct 1, 2003 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Jul 1, 2003 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Apr 1, 2003 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Jan 1, 2003 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Oct 1, 2002 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Nov 14, 2000 Resolved

Enforcement actions

Illinois regulators took 4 formal enforcement actions against Dixon between 2003 and 2009, filed as 5 records in EPA's data. The most recent was a signed compliance agreement in January 2009.

Date By Action Violations covered
Jan 2, 2009 Illinois Signed compliance agreement 6 violations (6 health-based): Arsenic
May 20, 2005 Illinois Signed compliance agreement 7 violations (7 health-based): Gross Alpha, Excl. Radon and U
Feb 2, 2004 Illinois Signed compliance agreement 27 violations (27 health-based): Combined Radium (-226 and -228)
Jan 4, 2003 Illinois Signed compliance agreement 2 violations (2 health-based): Combined Radium (-226 and -228)

Where the water comes from

Dixon draws water from 7 wells. 3 smaller public systems such as schools, businesses or campgrounds buy water from Dixon.

Annual water quality report

Dixon must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Systems serving 10,000 or more people must mail or deliver the report to every customer, and from 2027 they must send it twice a year.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water

To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Illinois.