Public water system record
Geneseo Hickory Hills HOA
Serves an area of Henry County, IL · 83 people served
Federal records show 12 health-based violations and 14 monitoring/reporting issues for Geneseo Hickory Hills HOA in the last ten years. The most serious issue in this window was a Arsenic violation that EPA lists as archived, not resolved.
System profile
- Health-based violations, last 10 years
- 12
- Resolved
- 10
- Unresolved
- 0
- Archived by EPA
- 2
- Any acute record
- No
- Monitoring issues, last 10 years
- 14
Key facts
- Geneseo Hickory Hills HOA draws water from 1 well.
- Highest measured level in the last 10 years: Arsenic, 0.016 mg/L, federal limit 0.01 mg/L (1.6 times the limit), 2021.
- Most recent formal enforcement: compliance order (no penalty) by EPA, February 2014.
- Record on file since 1995, with 25 health-based violations before October 19, 2016.
- Lead pipe inventory: 0 lead and 0 unknown out of 32 service lines.
Check whether Geneseo Hickory Hills HOA serves your address
Health-based violations
Since October 2016Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.
| Contaminant | Rule family | Start date | Status | Acute |
|---|---|---|---|---|
|
Arsenic
Contaminant limit exceeded
Measured 11.925 µg/L, federal limit 10 µg/L (1.2 times the limit)
|
330 | Jul 1, 2025 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 13.575 µg/L, federal limit 10 µg/L (1.4 times the limit)
|
330 | Apr 1, 2025 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.011 mg/L, federal limit 0.01 mg/L (1.1 times the limit)
|
330 | Jan 1, 2022 | Resolved | No |
|
Arsenic
Contaminant limit exceeded
Measured 0.016 mg/L, federal limit 0.01 mg/L (1.6 times the limit)
|
330 | Oct 1, 2021 | Resolved | No |
|
Arsenic
Contaminant limit exceeded
Measured 0.016 mg/L, federal limit 0.01 mg/L (1.6 times the limit)
|
330 | Jul 1, 2021 | Resolved | No |
|
Arsenic
Contaminant limit exceeded
Measured 0.015 mg/L, federal limit 0.01 mg/L (1.5 times the limit)
|
330 | Apr 1, 2021 | Resolved | No |
|
Arsenic
Contaminant limit exceeded
Measured 0.012 mg/L, federal limit 0.01 mg/L (1.2 times the limit)
|
330 | Apr 1, 2020 | Resolved | No |
|
Arsenic
Contaminant limit exceeded
Measured 0.012 mg/L, federal limit 0.01 mg/L (1.2 times the limit)
|
330 | Jan 1, 2020 | Resolved | No |
|
Arsenic
Contaminant limit exceeded
Measured 0.014 mg/L, federal limit 0.01 mg/L (1.4 times the limit)
|
330 | Jul 1, 2019 | Resolved | No |
|
Arsenic
Contaminant limit exceeded
Measured 0.016 mg/L, federal limit 0.01 mg/L (1.6 times the limit)
|
330 | Apr 1, 2019 | Resolved | No |
|
Arsenic
Contaminant limit exceeded
Measured 0.016 mg/L, federal limit 0.01 mg/L (1.6 times the limit)
|
330 | Jan 1, 2019 | Resolved | No |
|
Arsenic
Contaminant limit exceeded
Measured 0.015 mg/L, federal limit 0.01 mg/L (1.5 times the limit)
|
330 | Oct 1, 2018 | Resolved | No |
Monitoring and reporting issues
Since October 2016Missed tests or reports, not contaminants found above a limit.
| Issue | Start date | Status |
|---|---|---|
|
Lead and Copper Rule
Monitoring and reporting
|
Jun 30, 2025 | Active |
|
Lead and Copper Rule
Monitoring and reporting
|
Oct 1, 2023 | Resolved |
|
Lead and Copper Rule
Monitoring and reporting
|
Jul 1, 2023 | Resolved |
|
Lead and Copper Rule
Monitoring and reporting
|
Sep 29, 2021 | Resolved |
|
Consumer Confidence Rule
OTHER
|
Jul 1, 2021 | Resolved |
|
Arsenic
Monitoring and reporting
|
Apr 1, 2021 | Resolved |
|
Chlorine
Monitoring and reporting
|
Jul 1, 2020 | Resolved |
|
Revised Total Coliform Rule
Monitoring violation
|
Jul 1, 2020 | Resolved |
|
Public Notice
OTHER
|
Jul 12, 2019 | Resolved |
|
Consumer Confidence Rule
OTHER
|
Jul 1, 2019 | Resolved |
|
Consumer Confidence Rule
OTHER
|
Jul 1, 2019 | Resolved |
|
Public Notice
OTHER
|
Feb 15, 2019 | Resolved |
|
Consumer Confidence Rule
OTHER
|
Jul 1, 2018 | Resolved |
|
Consumer Confidence Rule
OTHER
|
Jul 1, 2017 | Resolved |
Full record since 1995
EPA's records for Geneseo Hickory Hills HOA go back to 1995. Before October 19, 2016 they list 25 health-based violations (17 resolved, 8 archived by EPA without a recorded fix) and 5 monitoring or reporting violations.
| Violations that began in | Health-based | Monitoring and reporting |
|---|---|---|
| 1990s | 0 | 1 |
| 2000s | 10 | 1 |
| 2010 to October 18, 2016 | 15 | 3 |
| October 19, 2016 to 2019 | 4 | 6 |
| 2020s | 8 | 8 |
Most recent health-based violation before October 19, 2016: Arsenic, began January 2016, Resolved.
Show all 25 health-based violations before October 19, 2016
| Contaminant | Start date | Status |
|---|---|---|
|
Arsenic
Contaminant limit exceeded
Measured 0.014 mg/L, federal limit 0.01 mg/L (1.4 times the limit)
|
Jan 1, 2016 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.017 mg/L, federal limit 0.01 mg/L (1.7 times the limit)
|
Oct 1, 2015 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.021 mg/L, federal limit 0.01 mg/L (2.1 times the limit)
|
Jul 1, 2015 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.025 mg/L, federal limit 0.01 mg/L (2.5 times the limit)
|
Apr 1, 2015 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.024 mg/L, federal limit 0.01 mg/L (2.4 times the limit)
|
Jan 1, 2015 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.025 mg/L, federal limit 0.01 mg/L (2.5 times the limit)
|
Oct 1, 2014 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.025 mg/L, federal limit 0.01 mg/L (2.5 times the limit)
|
Jul 1, 2014 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.026 mg/L, federal limit 0.01 mg/L (2.6 times the limit)
|
Apr 1, 2014 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.024 mg/L, federal limit 0.01 mg/L (2.4 times the limit)
|
Jan 1, 2014 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.019 mg/L, federal limit 0.01 mg/L (1.9 times the limit)
|
Oct 1, 2013 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.011 mg/L, federal limit 0.01 mg/L (1.1 times the limit)
|
Jul 1, 2013 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.012 mg/L, federal limit 0.01 mg/L (1.2 times the limit)
|
Oct 1, 2011 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.012 mg/L, federal limit 0.01 mg/L (1.2 times the limit)
|
Jul 1, 2011 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.011 mg/L, federal limit 0.01 mg/L (1.1 times the limit)
|
Apr 1, 2010 | Archived |
|
Arsenic
Contaminant limit exceeded
Measured 0.016 mg/L, federal limit 0.01 mg/L (1.6 times the limit)
|
Jan 1, 2010 | Archived |
|
Arsenic
Contaminant limit exceeded
Measured 0.021 mg/L, federal limit 0.01 mg/L (2.1 times the limit)
|
Oct 1, 2009 | Archived |
|
Arsenic
Contaminant limit exceeded
Measured 0.024 mg/L, federal limit 0.01 mg/L (2.4 times the limit)
|
Jul 1, 2009 | Archived |
|
Arsenic
Contaminant limit exceeded
Measured 0.019 mg/L, federal limit 0.01 mg/L (1.9 times the limit)
|
Apr 1, 2009 | Archived |
|
Arsenic
Contaminant limit exceeded
Measured 0.015 mg/L, federal limit 0.01 mg/L (1.5 times the limit)
|
Jan 1, 2009 | Archived |
|
Arsenic
Contaminant limit exceeded
Measured 0.011 mg/L, federal limit 0.01 mg/L (1.1 times the limit)
|
Oct 1, 2008 | Archived |
|
Arsenic
Contaminant limit exceeded
Measured 0.011 mg/L, federal limit 0.01 mg/L (1.1 times the limit)
|
Jul 1, 2008 | Archived |
|
Arsenic
Contaminant limit exceeded
Measured 0.015 mg/L, federal limit 0.01 mg/L (1.5 times the limit)
|
Oct 1, 2006 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.021 mg/L, federal limit 0.01 mg/L (2.1 times the limit)
|
Jul 1, 2006 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.025 mg/L, federal limit 0.01 mg/L (2.5 times the limit)
|
Apr 1, 2006 | Resolved |
|
Arsenic
Contaminant limit exceeded
Measured 0.03 mg/L, federal limit 0.01 mg/L (3 times the limit)
|
Jan 23, 2006 | Resolved |
Enforcement actions
Illinois regulators and EPA took 4 formal enforcement actions against Geneseo Hickory Hills HOA between 2006 and 2014. The most recent was a compliance order (no penalty) in February 2014.
| Date | By | Action | Violations covered |
|---|---|---|---|
| Feb 14, 2014 | EPA | Compliance order (no penalty) | 4 violations (4 health-based): Arsenic |
| Feb 16, 2012 | Illinois | Signed compliance agreement | 13 violations (13 health-based): Arsenic |
| Feb 19, 2009 | Illinois | Signed compliance agreement | 8 violations (8 health-based): Arsenic |
| Jun 8, 2006 | Illinois | Signed compliance agreement | 4 violations (4 health-based): Arsenic |
What the violations mean
Arsenic
12 incidentsArsenic exceeded the federal limit
Long-term arsenic exposure is linked to cancer and cardiovascular effects
Where the water comes from
Geneseo Hickory Hills HOA draws water from 1 well.
Annual water quality report
Geneseo Hickory Hills HOA must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.
Systems serving 500 or fewer people may meet the rule by telling customers the report is available on request, so you may need to ask Geneseo Hickory Hills HOA for a copy.
Find a posted report with EPA's Consumer Confidence Report search
Testing your own water
To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Illinois.
Certified drinking water labs by state EPA guidance for private wells