Public water system record

De Witt

Serves De Witt, De Witt County, IL · 175 people served

Federal records show 1 health-based violation and 2 monitoring/reporting issues for De Witt in the last ten years. The most serious issue in this window was a resolved Lead and Copper Rule violation.

  • IL0390100
  • CLINTON
  • IL
  • 175 served

System profile

Source water Groundwater
ZIP 61727
EPA system ID IL0390100

Verify this system on EPA ECHO →

Health-based violations, last 10 years
1
Resolved
1
Unresolved
0
Any acute record
No
Monitoring issues, last 10 years
2

Key facts

  • De Witt draws water from 1 well.
  • Most recent formal enforcement: compliance order (no penalty) by EPA, September 2012.
  • Record on file since 1992, with 38 health-based violations before October 19, 2016.

Check whether De Witt serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

Contaminant Rule family Start date Status Acute
Lead and Copper Rule
Treatment technique failure
350 Apr 2, 2025 Resolved No

Monitoring and reporting issues

Since October 2016

Missed tests or reports, not contaminants found above a limit.

Issue Start date Status
Public Notice
OTHER
Nov 1, 2025 Resolved
Lead and Copper Rule
Monitoring and reporting
Dec 30, 2018 Resolved

Full record since 1992

EPA's records for De Witt go back to 1992. Before October 19, 2016 they list 38 health-based violations (29 resolved, 9 archived by EPA without a recorded fix) and 38 monitoring or reporting violations.

Violations that began in Health-based Monitoring and reporting
1990s 9 24
2000s 18 12
2010 to October 18, 2016 11 2
October 19, 2016 to 2019 0 1
2020s 1 1

Most recent health-based violation before October 19, 2016: Arsenic, began April 2014, Resolved.

Show all 38 health-based violations before October 19, 2016
Contaminant Start date Status
Arsenic
Contaminant limit exceeded
Measured 0.011 mg/L, federal limit 0.01 mg/L (1.1 times the limit)
Apr 1, 2014 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.011 mg/L, federal limit 0.01 mg/L (1.1 times the limit)
Apr 1, 2012 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.014 mg/L, federal limit 0.01 mg/L (1.4 times the limit)
Jan 1, 2012 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.015 mg/L, federal limit 0.01 mg/L (1.5 times the limit)
Oct 1, 2011 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.015 mg/L, federal limit 0.01 mg/L (1.5 times the limit)
Jul 1, 2011 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.015 mg/L, federal limit 0.01 mg/L (1.5 times the limit)
Apr 1, 2011 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.012 mg/L, federal limit 0.01 mg/L (1.2 times the limit)
Jan 1, 2011 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.011 mg/L, federal limit 0.01 mg/L (1.1 times the limit)
Oct 1, 2010 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.011 mg/L, federal limit 0.01 mg/L (1.1 times the limit)
Jul 1, 2010 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.012 mg/L, federal limit 0.01 mg/L (1.2 times the limit)
Apr 1, 2010 Resolved
Arsenic
Contaminant limit exceeded
Jan 1, 2010 Resolved
Arsenic
Contaminant limit exceeded
Oct 1, 2009 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.017 mg/L, federal limit 0.01 mg/L (1.7 times the limit)
Jul 1, 2009 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.016 mg/L, federal limit 0.01 mg/L (1.6 times the limit)
Apr 1, 2009 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.019 mg/L, federal limit 0.01 mg/L (1.9 times the limit)
Jan 1, 2009 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.016 mg/L, federal limit 0.01 mg/L (1.6 times the limit)
Oct 1, 2008 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.016 mg/L, federal limit 0.01 mg/L (1.6 times the limit)
Jul 1, 2008 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.015 mg/L, federal limit 0.01 mg/L (1.5 times the limit)
Apr 1, 2008 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.014 mg/L, federal limit 0.01 mg/L (1.4 times the limit)
Jan 1, 2008 Resolved
Total Coliform
Contaminant limit exceeded
Jan 1, 2008 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.014 mg/L, federal limit 0.01 mg/L (1.4 times the limit)
Oct 1, 2007 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.011 mg/L, federal limit 0.01 mg/L (1.1 times the limit)
Jul 1, 2007 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.013 mg/L, federal limit 0.01 mg/L (1.3 times the limit)
Apr 1, 2007 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.013 mg/L, federal limit 0.01 mg/L (1.3 times the limit)
Jan 1, 2007 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.014 mg/L, federal limit 0.01 mg/L (1.4 times the limit)
Oct 1, 2006 Resolved
Total Coliform
Contaminant limit exceeded
Aug 1, 2006 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.018 mg/L, federal limit 0.01 mg/L (1.8 times the limit)
Jul 1, 2006 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.02 mg/L, federal limit 0.01 mg/L (2 times the limit)
Apr 1, 2006 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.02 mg/L, federal limit 0.01 mg/L (2 times the limit)
Jan 23, 2006 Resolved
Total Coliform
Contaminant limit exceeded
Jun 1, 1999 Archived
Total Coliform (acute)
Contaminant limit exceeded
Jun 1, 1999 Archived
Total Coliform
Contaminant limit exceeded
Sep 1, 1998 Archived
Total Coliform
Contaminant limit exceeded
Jul 1, 1998 Archived
Total Coliform
Contaminant limit exceeded
Aug 1, 1997 Archived
Total Coliform
Contaminant limit exceeded
Jun 1, 1994 Archived
Total Coliform (acute)
Contaminant limit exceeded
Jun 1, 1994 Archived
Total Coliform
Contaminant limit exceeded
Sep 1, 1993 Archived
Total Coliform
Contaminant limit exceeded
Sep 1, 1992 Archived

Enforcement actions

Illinois regulators and EPA took 2 formal enforcement actions against De Witt between 2006 and 2012. The most recent was a compliance order (no penalty) in September 2012.

Date By Action Violations covered
Sep 27, 2012 EPA Compliance order (no penalty) 27 violations (27 health-based): Arsenic
Jun 20, 2006 Illinois Signed compliance agreement 11 violations (11 health-based): Arsenic

What the violations mean

Lead and Copper Rule

1 incident

The system did not complete a treatment step or action that the Lead and Copper Rule requires (a treatment technique violation).

The utility had to notify customers about this violation.

Where the water comes from

De Witt draws water from 1 well.

Annual water quality report

De Witt must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Systems serving 500 or fewer people may meet the rule by telling customers the report is available on request, so you may need to ask De Witt for a copy.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water

To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Illinois.