Public water system record
Yankeetown WTP
Serves an area of Levy County, FL that includes Yankeetown · 711 people served
Federal records show 5 health-based violations and 8 monitoring/reporting issues for Yankeetown WTP in the last ten years. The most serious issue in this window was a Total Trihalomethanes (TTHMs) violation that EPA lists as archived, not resolved.
System profile
- Health-based violations, last 10 years
- 5
- Resolved
- 4
- Unresolved
- 0
- Archived by EPA
- 1
- Any acute record
- No
- Monitoring issues, last 10 years
- 8
Key facts
- Yankeetown WTP draws water from 7 wells.
- Highest measured level in the last 10 years: Total Trihalomethanes (TTHMs), 125.7625 µg/L, federal limit 80 µg/L (1.6 times the limit), 2019.
- Most recent formal enforcement: compliance order (no penalty) by EPA, June 2011.
- Record on file since 1987, with 27 health-based violations before October 19, 2016.
- Lead pipe inventory: 0 lead and 0 unknown out of 865 service lines.
Check whether Yankeetown WTP serves your address
Health-based violations
Since October 2016Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.
| Contaminant | Rule family | Start date | Status | Acute |
|---|---|---|---|---|
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 80.64 µg/L, federal limit 80 µg/L (at or just above the limit)
|
220 | Jan 1, 2024 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 111.9875 µg/L, federal limit 80 µg/L (1.4 times the limit)
|
220 | Oct 1, 2019 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 122.3875 µg/L, federal limit 80 µg/L (1.5 times the limit)
|
220 | Jul 1, 2019 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 125.7625 µg/L, federal limit 80 µg/L (1.6 times the limit)
|
220 | Apr 1, 2019 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 107.69 µg/L, federal limit 80 µg/L (1.3 times the limit)
|
220 | Jan 1, 2019 | Resolved | No |
Monitoring and reporting issues
Since October 2016Missed tests or reports, not contaminants found above a limit.
| Issue | Start date | Status |
|---|---|---|
|
E. coli
Monitoring and reporting
|
Feb 1, 2024 | Resolved |
|
Revised Total Coliform Rule
Monitoring violation
|
Feb 1, 2024 | Resolved |
|
Haloacetic Acids (HAA5)
Monitoring and reporting
|
Oct 1, 2023 | Resolved |
|
Total Trihalomethanes (TTHMs)
Monitoring and reporting
|
Oct 1, 2023 | Resolved |
|
E. coli
Monitoring and reporting
|
Apr 1, 2021 | Resolved |
|
Lead and Copper Rule
Monitoring and reporting
|
Jan 1, 2020 | Resolved |
|
Total Trihalomethanes (TTHMs)
Monitoring and reporting
|
Jan 1, 2017 | Resolved |
|
Haloacetic Acids (HAA5)
Monitoring and reporting
|
Jan 1, 2017 | Resolved |
Full record since 1987
EPA's records for Yankeetown WTP go back to 1987. Before October 19, 2016 they list 27 health-based violations (27 resolved) and 13 monitoring or reporting violations.
| Violations that began in | Health-based | Monitoring and reporting |
|---|---|---|
| 1980s | 0 | 8 |
| 1990s | 0 | 1 |
| 2000s | 27 | 0 |
| 2010 to October 18, 2016 | 0 | 4 |
| October 19, 2016 to 2019 | 4 | 2 |
| 2020s | 1 | 6 |
Most recent health-based violation before October 19, 2016: Total Trihalomethanes (TTHMs), began July 2009, Resolved.
Show all 27 health-based violations before October 19, 2016
| Contaminant | Start date | Status |
|---|---|---|
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 81.2825 µg/L, federal limit 80 µg/L (at or just above the limit)
|
Jul 1, 2009 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 119.6 µg/L, federal limit 80 µg/L (1.5 times the limit)
|
Apr 1, 2009 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 149.5 µg/L, federal limit 80 µg/L (1.9 times the limit)
|
Jan 1, 2009 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 75.425 µg/L, federal limit 60 µg/L (1.3 times the limit)
|
Jan 1, 2009 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 149.5 µg/L, federal limit 80 µg/L (1.9 times the limit)
|
Jan 1, 2009 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 75.4 µg/L, federal limit 60 µg/L (1.3 times the limit)
|
Jan 1, 2009 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 91.625 µg/L, federal limit 60 µg/L (1.5 times the limit)
|
Oct 1, 2008 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 179.325 µg/L, federal limit 80 µg/L (2.2 times the limit)
|
Oct 1, 2008 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 92.425 µg/L, federal limit 60 µg/L (1.5 times the limit)
|
Jul 1, 2008 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 163.25 µg/L, federal limit 80 µg/L (2 times the limit)
|
Jul 1, 2008 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 73.325 µg/L, federal limit 60 µg/L (1.2 times the limit)
|
Apr 1, 2008 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 139.525 µg/L, federal limit 80 µg/L (1.7 times the limit)
|
Apr 1, 2008 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 61.425 µg/L, federal limit 60 µg/L (at or just above the limit)
|
Jan 1, 2008 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 153.875 µg/L, federal limit 80 µg/L (1.9 times the limit)
|
Jan 1, 2008 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 118.54 µg/L, federal limit 80 µg/L (1.5 times the limit)
|
Oct 1, 2007 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 122.96 µg/L, federal limit 80 µg/L (1.5 times the limit)
|
Jul 1, 2007 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 222.2 µg/L, federal limit 80 µg/L (2.8 times the limit)
|
Apr 1, 2007 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
|
Apr 1, 2007 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 152.8 µg/L, federal limit 80 µg/L (1.9 times the limit)
|
Jan 1, 2007 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 128.5 µg/L, federal limit 80 µg/L (1.6 times the limit)
|
Oct 1, 2006 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 308.1 µg/L, federal limit 80 µg/L (3.9 times the limit)
|
Jul 1, 2006 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 114 µg/L, federal limit 80 µg/L (1.4 times the limit)
|
Apr 1, 2006 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
|
Jan 1, 2006 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 164 µg/L, federal limit 80 µg/L (2.1 times the limit)
|
Oct 1, 2005 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 101.8 µg/L, federal limit 80 µg/L (1.3 times the limit)
|
Jul 1, 2005 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
|
Apr 1, 2005 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 102.92 µg/L, federal limit 80 µg/L (1.3 times the limit)
|
Jan 1, 2005 | Resolved |
Enforcement actions
Florida regulators and EPA took 2 formal enforcement actions against Yankeetown WTP between 2006 and 2011. The most recent was a compliance order (no penalty) in June 2011.
| Date | By | Action | Violations covered |
|---|---|---|---|
| Jun 7, 2011 | EPA | Compliance order (no penalty) | 1 violation: Stage 2 Disinfection Byproducts Rule |
| Sep 19, 2006 | Florida | Signed compliance agreement | 27 violations (27 health-based): Haloacetic Acids (HAA5), Total Trihalomethanes (TTHMs) |
What the violations mean
Total Trihalomethanes (TTHMs)
5 incidentsDisinfection byproduct levels exceeded the federal limit
Long-term TTHM exposure may increase bladder cancer risk
Where the water comes from
Yankeetown WTP draws water from 7 wells.
Annual water quality report
Yankeetown WTP must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.
Where the state allows it, systems serving fewer than 10,000 people may publish the report in a local newspaper or news site instead of mailing it, and must provide a copy on request.
Find a posted report with EPA's Consumer Confidence Report search
Testing your own water
To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Florida.