Public water system record

Yankeetown WTP

Serves an area of Levy County, FL that includes Yankeetown · 711 people served

Federal records show 5 health-based violations and 8 monitoring/reporting issues for Yankeetown WTP in the last ten years. The most serious issue in this window was a Total Trihalomethanes (TTHMs) violation that EPA lists as archived, not resolved.

  • FL6382116
  • YANKEETOWN
  • FL
  • 711 served

System profile

Source water Groundwater
ZIP 34498
EPA system ID FL6382116

Verify this system on EPA ECHO →

Health-based violations, last 10 years
5
Resolved
4
Unresolved
0
Archived by EPA
1
Any acute record
No
Monitoring issues, last 10 years
8

Key facts

  • Yankeetown WTP draws water from 7 wells.
  • Highest measured level in the last 10 years: Total Trihalomethanes (TTHMs), 125.7625 µg/L, federal limit 80 µg/L (1.6 times the limit), 2019.
  • Most recent formal enforcement: compliance order (no penalty) by EPA, June 2011.
  • Record on file since 1987, with 27 health-based violations before October 19, 2016.
  • Lead pipe inventory: 0 lead and 0 unknown out of 865 service lines.

Check whether Yankeetown WTP serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

Contaminant Rule family Start date Status Acute
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 80.64 µg/L, federal limit 80 µg/L (at or just above the limit)
220 Jan 1, 2024 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 111.9875 µg/L, federal limit 80 µg/L (1.4 times the limit)
220 Oct 1, 2019 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 122.3875 µg/L, federal limit 80 µg/L (1.5 times the limit)
220 Jul 1, 2019 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 125.7625 µg/L, federal limit 80 µg/L (1.6 times the limit)
220 Apr 1, 2019 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 107.69 µg/L, federal limit 80 µg/L (1.3 times the limit)
220 Jan 1, 2019 Resolved No

Monitoring and reporting issues

Since October 2016

Missed tests or reports, not contaminants found above a limit.

Issue Start date Status
E. coli
Monitoring and reporting
Feb 1, 2024 Resolved
Revised Total Coliform Rule
Monitoring violation
Feb 1, 2024 Resolved
Haloacetic Acids (HAA5)
Monitoring and reporting
Oct 1, 2023 Resolved
Total Trihalomethanes (TTHMs)
Monitoring and reporting
Oct 1, 2023 Resolved
E. coli
Monitoring and reporting
Apr 1, 2021 Resolved
Lead and Copper Rule
Monitoring and reporting
Jan 1, 2020 Resolved
Total Trihalomethanes (TTHMs)
Monitoring and reporting
Jan 1, 2017 Resolved
Haloacetic Acids (HAA5)
Monitoring and reporting
Jan 1, 2017 Resolved

Full record since 1987

EPA's records for Yankeetown WTP go back to 1987. Before October 19, 2016 they list 27 health-based violations (27 resolved) and 13 monitoring or reporting violations.

Violations that began in Health-based Monitoring and reporting
1980s 0 8
1990s 0 1
2000s 27 0
2010 to October 18, 2016 0 4
October 19, 2016 to 2019 4 2
2020s 1 6

Most recent health-based violation before October 19, 2016: Total Trihalomethanes (TTHMs), began July 2009, Resolved.

Show all 27 health-based violations before October 19, 2016
Contaminant Start date Status
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 81.2825 µg/L, federal limit 80 µg/L (at or just above the limit)
Jul 1, 2009 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 119.6 µg/L, federal limit 80 µg/L (1.5 times the limit)
Apr 1, 2009 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 149.5 µg/L, federal limit 80 µg/L (1.9 times the limit)
Jan 1, 2009 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 75.425 µg/L, federal limit 60 µg/L (1.3 times the limit)
Jan 1, 2009 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 149.5 µg/L, federal limit 80 µg/L (1.9 times the limit)
Jan 1, 2009 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 75.4 µg/L, federal limit 60 µg/L (1.3 times the limit)
Jan 1, 2009 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 91.625 µg/L, federal limit 60 µg/L (1.5 times the limit)
Oct 1, 2008 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 179.325 µg/L, federal limit 80 µg/L (2.2 times the limit)
Oct 1, 2008 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 92.425 µg/L, federal limit 60 µg/L (1.5 times the limit)
Jul 1, 2008 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 163.25 µg/L, federal limit 80 µg/L (2 times the limit)
Jul 1, 2008 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 73.325 µg/L, federal limit 60 µg/L (1.2 times the limit)
Apr 1, 2008 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 139.525 µg/L, federal limit 80 µg/L (1.7 times the limit)
Apr 1, 2008 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 61.425 µg/L, federal limit 60 µg/L (at or just above the limit)
Jan 1, 2008 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 153.875 µg/L, federal limit 80 µg/L (1.9 times the limit)
Jan 1, 2008 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 118.54 µg/L, federal limit 80 µg/L (1.5 times the limit)
Oct 1, 2007 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 122.96 µg/L, federal limit 80 µg/L (1.5 times the limit)
Jul 1, 2007 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 222.2 µg/L, federal limit 80 µg/L (2.8 times the limit)
Apr 1, 2007 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Apr 1, 2007 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 152.8 µg/L, federal limit 80 µg/L (1.9 times the limit)
Jan 1, 2007 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 128.5 µg/L, federal limit 80 µg/L (1.6 times the limit)
Oct 1, 2006 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 308.1 µg/L, federal limit 80 µg/L (3.9 times the limit)
Jul 1, 2006 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 114 µg/L, federal limit 80 µg/L (1.4 times the limit)
Apr 1, 2006 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Jan 1, 2006 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 164 µg/L, federal limit 80 µg/L (2.1 times the limit)
Oct 1, 2005 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 101.8 µg/L, federal limit 80 µg/L (1.3 times the limit)
Jul 1, 2005 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Apr 1, 2005 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 102.92 µg/L, federal limit 80 µg/L (1.3 times the limit)
Jan 1, 2005 Resolved

Enforcement actions

Florida regulators and EPA took 2 formal enforcement actions against Yankeetown WTP between 2006 and 2011. The most recent was a compliance order (no penalty) in June 2011.

Date By Action Violations covered
Jun 7, 2011 EPA Compliance order (no penalty) 1 violation: Stage 2 Disinfection Byproducts Rule
Sep 19, 2006 Florida Signed compliance agreement 27 violations (27 health-based): Haloacetic Acids (HAA5), Total Trihalomethanes (TTHMs)

What the violations mean

Total Trihalomethanes (TTHMs)

5 incidents

Disinfection byproduct levels exceeded the federal limit

Long-term TTHM exposure may increase bladder cancer risk

Where the water comes from

Yankeetown WTP draws water from 7 wells.

Annual water quality report

Yankeetown WTP must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Where the state allows it, systems serving fewer than 10,000 people may publish the report in a local newspaper or news site instead of mailing it, and must provide a copy on request.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water

To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Florida.