Public water system record

Riverlandings Water Treatment Plant

On record as serving LaBelle, Hendry County, FL · Serves 134 people

Federal records show 21 health-based violations and 4 monitoring/reporting issues for Riverlandings Water Treatment Plant in the last ten years, including an unresolved LEAD AND COPPER RULE REVISIONS violation.

  • FL5264112
  • NAPLES
  • FL
  • 134 served

System profile

Source water Surface water
ZIP 34119
EPA system ID FL5264112

Verify this system on EPA ECHO →

Health-based violations, last 10 years
21
Resolved
20
Unresolved
1
Any acute record
No
Monitoring issues, last 10 years
4

Key facts

  • Riverlandings Water Treatment Plant draws water from 1 well and 1 surface water intake (1 of them for emergency, seasonal or other part-time use).
  • Highest measured level in the last 10 years: Haloacetic Acids (HAA5), 272.5 µg/L, federal limit 60 µg/L (4.5 times the limit), 2022.

Check whether Riverlandings Water Treatment Plant serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

Contaminant Rule family Start date Status Acute
LEAD AND COPPER RULE REVISIONS
Treatment technique failure
350 Feb 1, 2025 Active No
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 115.6 µg/L, federal limit 60 µg/L (1.9 times the limit)
220 Oct 1, 2022 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 133.75 µg/L, federal limit 80 µg/L (1.7 times the limit)
220 Oct 1, 2022 Resolved No
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 149.5 µg/L, federal limit 60 µg/L (2.5 times the limit)
220 Jul 1, 2022 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 168 µg/L, federal limit 80 µg/L (2.1 times the limit)
220 Jul 1, 2022 Resolved No
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 250.25 µg/L, federal limit 60 µg/L (4.2 times the limit)
220 Apr 1, 2022 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 277.5 µg/L, federal limit 80 µg/L (3.5 times the limit)
220 Apr 1, 2022 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 312.5 µg/L, federal limit 80 µg/L (3.9 times the limit)
220 Jan 1, 2022 Resolved No
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 272.5 µg/L, federal limit 60 µg/L (4.5 times the limit)
220 Jan 1, 2022 Resolved No
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 187.75 µg/L, federal limit 60 µg/L (3.1 times the limit)
220 Oct 1, 2021 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 260 µg/L, federal limit 80 µg/L (3.3 times the limit)
220 Oct 1, 2021 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 270 µg/L, federal limit 80 µg/L (3.4 times the limit)
220 Jul 1, 2021 Resolved No
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 190.25 µg/L, federal limit 60 µg/L (3.2 times the limit)
220 Jul 1, 2021 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 247.5 µg/L, federal limit 80 µg/L (3.1 times the limit)
220 Apr 1, 2021 Resolved No
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 165.25 µg/L, federal limit 60 µg/L (2.8 times the limit)
220 Apr 1, 2021 Resolved No
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 140.25 µg/L, federal limit 60 µg/L (2.3 times the limit)
220 Jan 1, 2021 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 182.5 µg/L, federal limit 80 µg/L (2.3 times the limit)
220 Jan 1, 2021 Resolved No
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 117.5 µg/L, federal limit 60 µg/L (2 times the limit)
220 Oct 1, 2020 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 140 µg/L, federal limit 80 µg/L (1.8 times the limit)
220 Oct 1, 2020 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 95 µg/L, federal limit 80 µg/L (1.2 times the limit)
220 Jul 1, 2020 Resolved No
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 80 µg/L, federal limit 60 µg/L (1.3 times the limit)
220 Jul 1, 2020 Resolved No

Monitoring and reporting issues

Since October 2016

Missed tests or reports, not contaminants found above a limit.

Issue Start date Status
LEAD AND COPPER RULE REVISIONS
RPT
Feb 1, 2025 Active
Total Trihalomethanes (TTHMs)
Monitoring and reporting
Oct 1, 2021 Resolved
Haloacetic Acids (HAA5)
Monitoring and reporting
Oct 1, 2021 Resolved
Nitrate
Monitoring and reporting
Jan 1, 2021 Resolved

What the violations mean

Haloacetic Acids (HAA5)

10 incidents

Haloacetic acid byproducts exceeded the federal limit

Long-term exposure to HAAs may increase cancer risk

Total Trihalomethanes (TTHMs)

10 incidents

Disinfection byproduct levels exceeded the federal limit

Long-term TTHM exposure may increase bladder cancer risk

LEAD AND COPPER RULE REVISIONS

1 incident

The system did not complete a treatment step or action that the LEAD AND COPPER RULE REVISIONS requires (a treatment technique violation).

The utility had to notify customers about this violation.

Where the water comes from

Riverlandings Water Treatment Plant draws water from 1 well and 1 surface water intake (1 of them for emergency, seasonal or other part-time use).

Annual water quality report

Riverlandings Water Treatment Plant must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Systems serving 500 or fewer people may meet the rule by telling customers the report is available on request, so you may need to ask Riverlandings Water Treatment Plant for a copy.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water