Public water system record
Marion Correctional Institution
Serves an area of Marion County, FL · 2,700 people served
Federal records show 15 health-based violations and 18 monitoring/reporting issues for Marion Correctional Institution in the last ten years. The most serious issue in this window was a Total Trihalomethanes (TTHMs) violation that EPA lists as archived, not resolved.
System profile
- Health-based violations, last 10 years
- 15
- Resolved
- 12
- Unresolved
- 0
- Archived by EPA
- 3
- Any acute record
- No
- Monitoring issues, last 10 years
- 18
Key facts
- Marion Correctional Institution draws water from 4 wells.
- Highest measured level in the last 10 years: Total Trihalomethanes (TTHMs), 151.5 µg/L, federal limit 80 µg/L (1.9 times the limit), 2018.
- Most recent formal enforcement: compliance order (no penalty) by Florida, October 2024.
- Record on file since 1991, with 19 health-based violations before October 19, 2016.
- Lead pipe inventory: 0 lead and 0 unknown out of 68 service lines.
Check whether Marion Correctional Institution serves your address
Health-based violations
Since October 2016Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.
| Contaminant | Rule family | Start date | Status | Acute |
|---|---|---|---|---|
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 82.9333 µg/L, federal limit 80 µg/L (at or just above the limit)
|
220 | Jul 1, 2022 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 86.225 µg/L, federal limit 80 µg/L (1.1 times the limit)
|
220 | Apr 1, 2022 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 88.075 µg/L, federal limit 80 µg/L (1.1 times the limit)
|
220 | Jan 1, 2022 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 90.95 µg/L, federal limit 80 µg/L (1.1 times the limit)
|
220 | Oct 1, 2021 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 82.75 µg/L, federal limit 80 µg/L (at or just above the limit)
|
220 | Jan 1, 2019 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 98.625 µg/L, federal limit 80 µg/L (1.2 times the limit)
|
220 | Oct 1, 2018 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 122.125 µg/L, federal limit 80 µg/L (1.5 times the limit)
|
220 | Jul 1, 2018 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 130.375 µg/L, federal limit 80 µg/L (1.6 times the limit)
|
220 | Apr 1, 2018 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 151.5 µg/L, federal limit 80 µg/L (1.9 times the limit)
|
220 | Jan 1, 2018 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 149.5 µg/L, federal limit 80 µg/L (1.9 times the limit)
|
220 | Oct 1, 2017 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 126.225 µg/L, federal limit 80 µg/L (1.6 times the limit)
|
220 | Jul 1, 2017 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 118.575 µg/L, federal limit 80 µg/L (1.5 times the limit)
|
220 | Apr 1, 2017 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 113.825 µg/L, federal limit 80 µg/L (1.4 times the limit)
|
220 | Jan 1, 2017 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 61.375 µg/L, federal limit 60 µg/L (at or just above the limit)
|
220 | Oct 1, 2016 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 99.05 µg/L, federal limit 80 µg/L (1.2 times the limit)
|
220 | Oct 1, 2016 | Resolved | No |
Monitoring and reporting issues
Since October 2016Missed tests or reports, not contaminants found above a limit.
| Issue | Start date | Status |
|---|---|---|
|
Revised Total Coliform Rule
Monitoring violation
|
Feb 1, 2023 | Resolved |
|
Nitrate
Monitoring and reporting
|
Jan 1, 2023 | Resolved |
|
Revised Total Coliform Rule
Monitoring violation
|
Jan 1, 2023 | Resolved |
|
Revised Total Coliform Rule
Monitoring violation
|
Dec 1, 2022 | Resolved |
|
Total Trihalomethanes (TTHMs)
Monitoring and reporting
|
Oct 1, 2022 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
|
Haloacetic Acids (HAA5)
Monitoring and reporting
|
Oct 1, 2022 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
|
Total Trihalomethanes (TTHMs)
Monitoring and reporting
|
Jul 1, 2022 | Resolved |
|
Haloacetic Acids (HAA5)
Monitoring and reporting
|
Jul 1, 2022 | Resolved |
|
Consumer Confidence Rule
OTHER
|
Jul 1, 2021 | Resolved |
|
Revised Total Coliform Rule
Monitoring violation
|
Jan 1, 2021 | Resolved |
|
Revised Total Coliform Rule
Monitoring violation
|
Jan 1, 2020 | Resolved |
|
Revised Total Coliform Rule
Monitoring violation
|
Dec 1, 2019 | Resolved |
|
Revised Total Coliform Rule
Monitoring violation
|
Nov 1, 2019 | Resolved |
|
Total Trihalomethanes (TTHMs)
Monitoring and reporting
|
Oct 1, 2019 | Resolved |
|
Haloacetic Acids (HAA5)
Monitoring and reporting
|
Oct 1, 2019 | Resolved |
|
Consumer Confidence Rule
OTHER
|
Jul 1, 2019 | Resolved |
|
Consumer Confidence Rule
OTHER
|
Jul 1, 2016 | Resolved |
|
Lead and Copper Rule
Monitoring and reporting
|
Jan 1, 2016 | Resolved |
Full record since 1991
EPA's records for Marion Correctional Institution go back to 1991. Before October 19, 2016 they list 19 health-based violations (17 resolved, 2 archived by EPA without a recorded fix) and 22 monitoring or reporting violations.
| Violations that began in | Health-based | Monitoring and reporting |
|---|---|---|
| 1990s | 0 | 3 |
| 2000s | 3 | 7 |
| 2010 to October 18, 2016 | 16 | 12 |
| October 19, 2016 to 2019 | 9 | 5 |
| 2020s | 4 | 11 |
Most recent health-based violation before October 19, 2016: Haloacetic Acids (HAA5), began October 2016, Resolved.
Show all 19 health-based violations before October 19, 2016
| Contaminant | Start date | Status |
|---|---|---|
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 61.375 µg/L, federal limit 60 µg/L (at or just above the limit)
|
Oct 1, 2016 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 99.05 µg/L, federal limit 80 µg/L (1.2 times the limit)
|
Oct 1, 2016 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 68.675 µg/L, federal limit 60 µg/L (1.1 times the limit)
|
Jul 1, 2016 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 108.725 µg/L, federal limit 80 µg/L (1.4 times the limit)
|
Jul 1, 2016 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 104.475 µg/L, federal limit 80 µg/L (1.3 times the limit)
|
Apr 1, 2016 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 80.3 µg/L, federal limit 60 µg/L (1.3 times the limit)
|
Apr 1, 2016 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
|
Jan 1, 2016 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 72.7 µg/L, federal limit 60 µg/L (1.2 times the limit)
|
Jan 1, 2016 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 94.3 µg/L, federal limit 60 µg/L (1.6 times the limit)
|
Oct 1, 2015 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 118 µg/L, federal limit 80 µg/L (1.5 times the limit)
|
Oct 1, 2015 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 73.525 µg/L, federal limit 60 µg/L (1.2 times the limit)
|
Jan 1, 2013 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 64.6075 µg/L, federal limit 60 µg/L (1.1 times the limit)
|
Oct 1, 2012 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 82.7 µg/L, federal limit 80 µg/L (at or just above the limit)
|
Jul 1, 2012 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 72.3325 µg/L, federal limit 60 µg/L (1.2 times the limit)
|
Jul 1, 2012 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 88.175 µg/L, federal limit 80 µg/L (1.1 times the limit)
|
Apr 1, 2012 | Resolved |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 71.4575 µg/L, federal limit 60 µg/L (1.2 times the limit)
|
Apr 1, 2012 | Resolved |
|
Total Coliform
Contaminant limit exceeded
|
Apr 1, 2009 | Resolved |
|
Total Coliform
Contaminant limit exceeded
|
Jun 1, 2002 | Archived |
|
Total Coliform
Contaminant limit exceeded
|
May 1, 2002 | Archived |
Enforcement actions
Florida regulators took 3 formal enforcement actions against Marion Correctional Institution between 2017 and 2024. The most recent was a compliance order (no penalty) in October 2024.
| Date | By | Action | Violations covered |
|---|---|---|---|
| Oct 15, 2024 | Florida | Compliance order (no penalty) | 1 violation: Nitrate |
| Mar 15, 2023 | Florida | Compliance order (no penalty) | 1 violation (1 health-based): Total Trihalomethanes (TTHMs) |
| Mar 8, 2017 | Florida | Compliance order (no penalty) | 19 violations (19 health-based): Haloacetic Acids (HAA5), Total Trihalomethanes (TTHMs) |
What the violations mean
Total Trihalomethanes (TTHMs)
14 incidentsDisinfection byproduct levels exceeded the federal limit
Long-term TTHM exposure may increase bladder cancer risk
Haloacetic Acids (HAA5)
1 incidentHaloacetic acid byproducts exceeded the federal limit
Long-term exposure to HAAs may increase cancer risk
Where the water comes from
Marion Correctional Institution draws water from 4 wells.
Annual water quality report
Marion Correctional Institution must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.
Where the state allows it, systems serving fewer than 10,000 people may publish the report in a local newspaper or news site instead of mailing it, and must provide a copy on request.
Find a posted report with EPA's Consumer Confidence Report search
Testing your own water
To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Florida.
Certified drinking water labs by state EPA guidance for private wells