Public water system record

South Swink Water Authority

On record as serving Otero County, CO · Serves 622 people

Federal records show 105 health-based violations and no monitoring/reporting issues for South Swink Water Authority in the last ten years. The most serious issue in this window was a Combined Radium (-226 and -228) violation that EPA lists as archived, not resolved.

  • CO0145690
  • LA JUNTA
  • CO
  • 622 served

System profile

Source water Groundwater
ZIP 81050
EPA system ID CO0145690

Verify this system on EPA ECHO →

Health-based violations, last 10 years
105
Resolved
26
Unresolved
0
Archived by EPA
79
Any acute record
No
Monitoring issues, last 10 years
0

Key facts

  • South Swink Water Authority draws water from 4 wells (1 of them for emergency, seasonal or other part-time use).
  • Highest measured level in the last 10 years: Combined Radium (-226 and -228), 23.4 pCi/L, federal limit 5 pCi/L (4.7 times the limit), 2017.
  • Most recent formal enforcement: compliance order (no penalty) by Colorado, May 2022.
  • Record on file since 1994, with 25 health-based violations before October 19, 2016.
  • Lead pipe inventory: 0 lead and 0 unknown out of 227 service lines.

Check whether South Swink Water Authority serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

Contaminant Rule family Start date Status Acute
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 20 pCi/L, federal limit 5 pCi/L (4 times the limit)
340 Oct 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 14 pCi/L, federal limit 5 pCi/L (2.8 times the limit)
340 Oct 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 17.2 pCi/L, federal limit 15 pCi/L (1.1 times the limit)
340 Apr 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 19 pCi/L, federal limit 5 pCi/L (3.8 times the limit)
340 Apr 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 12 pCi/L, federal limit 5 pCi/L (2.4 times the limit)
340 Apr 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 18.45 pCi/L, federal limit 15 pCi/L (1.2 times the limit)
340 Jan 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 13.1 pCi/L, federal limit 5 pCi/L (2.6 times the limit)
340 Jan 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 19.5 pCi/L, federal limit 5 pCi/L (3.9 times the limit)
340 Jan 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 13.65 pCi/L, federal limit 5 pCi/L (2.7 times the limit)
340 Oct 1, 2024 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 19.75 pCi/L, federal limit 15 pCi/L (1.3 times the limit)
340 Oct 1, 2024 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 19.2 pCi/L, federal limit 5 pCi/L (3.8 times the limit)
340 Oct 1, 2024 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 19.02 pCi/L, federal limit 15 pCi/L (1.3 times the limit)
340 Jul 1, 2024 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 13.75 pCi/L, federal limit 5 pCi/L (2.8 times the limit)
340 Jul 1, 2024 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 18.38 pCi/L, federal limit 5 pCi/L (3.7 times the limit)
340 Jul 1, 2024 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 13.85 pCi/L, federal limit 5 pCi/L (2.8 times the limit)
340 Apr 1, 2024 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 17.55 pCi/L, federal limit 5 pCi/L (3.5 times the limit)
340 Apr 1, 2024 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 18.3 pCi/L, federal limit 15 pCi/L (1.2 times the limit)
340 Apr 1, 2024 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 14.53 pCi/L, federal limit 5 pCi/L (2.9 times the limit)
340 Jan 1, 2024 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 17.9 pCi/L, federal limit 5 pCi/L (3.6 times the limit)
340 Jan 1, 2024 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 18.15 pCi/L, federal limit 15 pCi/L (1.2 times the limit)
340 Jan 1, 2024 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 15.2 pCi/L, federal limit 5 pCi/L (3 times the limit)
340 Oct 1, 2023 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 18 pCi/L, federal limit 15 pCi/L (1.2 times the limit)
340 Oct 1, 2023 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 18.25 pCi/L, federal limit 5 pCi/L (3.7 times the limit)
340 Oct 1, 2023 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 15.2 pCi/L, federal limit 5 pCi/L (3 times the limit)
340 Jul 1, 2023 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 18 pCi/L, federal limit 15 pCi/L (1.2 times the limit)
340 Jul 1, 2023 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 18.25 pCi/L, federal limit 5 pCi/L (3.7 times the limit)
340 Jul 1, 2023 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 16.1 pCi/L, federal limit 15 pCi/L (1.1 times the limit)
340 Apr 1, 2023 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 16.5 pCi/L, federal limit 5 pCi/L (3.3 times the limit)
340 Apr 1, 2023 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 18.4 pCi/L, federal limit 15 pCi/L (1.2 times the limit)
340 Apr 1, 2023 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 20.7 pCi/L, federal limit 5 pCi/L (4.1 times the limit)
340 Apr 1, 2023 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 16.1 pCi/L, federal limit 15 pCi/L (1.1 times the limit)
340 Jan 1, 2023 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 16.5 pCi/L, federal limit 5 pCi/L (3.3 times the limit)
340 Jan 1, 2023 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 18.4 pCi/L, federal limit 15 pCi/L (1.2 times the limit)
340 Jan 1, 2023 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 20.5 pCi/L, federal limit 5 pCi/L (4.1 times the limit)
340 Jan 1, 2023 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 16 pCi/L, federal limit 15 pCi/L (1.1 times the limit)
340 Oct 1, 2022 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 19 pCi/L, federal limit 5 pCi/L (3.8 times the limit)
340 Oct 1, 2022 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 14 pCi/L, federal limit 5 pCi/L (2.8 times the limit)
340 Oct 1, 2022 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 20 pCi/L, federal limit 5 pCi/L (4 times the limit)
340 Jul 1, 2022 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 14 pCi/L, federal limit 5 pCi/L (2.8 times the limit)
340 Jul 1, 2022 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 14 pCi/L, federal limit 5 pCi/L (2.8 times the limit)
340 Apr 1, 2022 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 21 pCi/L, federal limit 5 pCi/L (4.2 times the limit)
340 Apr 1, 2022 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 13 pCi/L, federal limit 5 pCi/L (2.6 times the limit)
340 Jan 1, 2022 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 21 pCi/L, federal limit 5 pCi/L (4.2 times the limit)
340 Jan 1, 2022 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 13 pCi/L, federal limit 5 pCi/L (2.6 times the limit)
340 Oct 1, 2021 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 21 pCi/L, federal limit 5 pCi/L (4.2 times the limit)
340 Oct 1, 2021 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 15.5 pCi/L, federal limit 15 pCi/L (at or just above the limit)
340 Jul 1, 2021 Resolved No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 20.27 pCi/L, federal limit 5 pCi/L (4.1 times the limit)
340 Jul 1, 2021 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 14 pCi/L, federal limit 5 pCi/L (2.8 times the limit)
340 Jul 1, 2021 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 15 pCi/L, federal limit 5 pCi/L (3 times the limit)
340 Apr 1, 2021 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 16 pCi/L, federal limit 15 pCi/L (1.1 times the limit)
340 Apr 1, 2021 Resolved No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 19 pCi/L, federal limit 15 pCi/L (1.3 times the limit)
340 Apr 1, 2021 Resolved No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 20 pCi/L, federal limit 5 pCi/L (4 times the limit)
340 Apr 1, 2021 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 19 pCi/L, federal limit 15 pCi/L (1.3 times the limit)
340 Jan 1, 2021 Resolved No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 21 pCi/L, federal limit 5 pCi/L (4.2 times the limit)
340 Jan 1, 2021 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 16 pCi/L, federal limit 5 pCi/L (3.2 times the limit)
340 Jan 1, 2021 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 25 pCi/L, federal limit 15 pCi/L (1.7 times the limit)
340 Jan 1, 2021 Resolved No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 16 pCi/L, federal limit 5 pCi/L (3.2 times the limit)
340 Oct 1, 2020 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 31 pCi/L, federal limit 15 pCi/L (2.1 times the limit)
340 Oct 1, 2020 Resolved No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 22 pCi/L, federal limit 5 pCi/L (4.4 times the limit)
340 Oct 1, 2020 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 22.1 pCi/L, federal limit 15 pCi/L (1.5 times the limit)
340 Oct 1, 2020 Resolved No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 30 pCi/L, federal limit 15 pCi/L (2 times the limit)
340 Jul 1, 2020 Resolved No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 16 pCi/L, federal limit 5 pCi/L (3.2 times the limit)
340 Jul 1, 2020 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 22 pCi/L, federal limit 5 pCi/L (4.4 times the limit)
340 Jul 1, 2020 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 19 pCi/L, federal limit 15 pCi/L (1.3 times the limit)
340 Jul 1, 2020 Resolved No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 16.3 pCi/L, federal limit 5 pCi/L (3.3 times the limit)
340 Apr 1, 2020 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 22.1 pCi/L, federal limit 5 pCi/L (4.4 times the limit)
340 Apr 1, 2020 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 29 pCi/L, federal limit 15 pCi/L (1.9 times the limit)
340 Apr 1, 2020 Resolved No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 16.05 pCi/L, federal limit 5 pCi/L (3.2 times the limit)
340 Jan 1, 2020 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 21.92 pCi/L, federal limit 5 pCi/L (4.4 times the limit)
340 Jan 1, 2020 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 26.75 pCi/L, federal limit 15 pCi/L (1.8 times the limit)
340 Jan 1, 2020 Resolved No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 16.9 pCi/L, federal limit 5 pCi/L (3.4 times the limit)
340 Oct 1, 2019 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 21.6 pCi/L, federal limit 5 pCi/L (4.3 times the limit)
340 Oct 1, 2019 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 22 pCi/L, federal limit 15 pCi/L (1.5 times the limit)
340 Oct 1, 2019 Resolved No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 16.9 pCi/L, federal limit 5 pCi/L (3.4 times the limit)
340 Jul 1, 2019 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 21.6 pCi/L, federal limit 5 pCi/L (4.3 times the limit)
340 Jul 1, 2019 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 22 pCi/L, federal limit 15 pCi/L (1.5 times the limit)
340 Jul 1, 2019 Resolved No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 14.55 pCi/L, federal limit 5 pCi/L (2.9 times the limit)
340 Apr 1, 2019 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 18 pCi/L, federal limit 15 pCi/L (1.2 times the limit)
340 Apr 1, 2019 Resolved No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 20.8 pCi/L, federal limit 5 pCi/L (4.2 times the limit)
340 Apr 1, 2019 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 29 pCi/L, federal limit 15 pCi/L (1.9 times the limit)
340 Apr 1, 2019 Resolved No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 14.63 pCi/L, federal limit 5 pCi/L (2.9 times the limit)
340 Jan 1, 2019 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 17.25 pCi/L, federal limit 15 pCi/L (1.2 times the limit)
340 Jan 1, 2019 Resolved No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 21.15 pCi/L, federal limit 5 pCi/L (4.2 times the limit)
340 Jan 1, 2019 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 25.75 pCi/L, federal limit 15 pCi/L (1.7 times the limit)
340 Jan 1, 2019 Resolved No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 22.5 pCi/L, federal limit 15 pCi/L (1.5 times the limit)
340 Oct 1, 2018 Resolved No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 16.5 pCi/L, federal limit 15 pCi/L (1.1 times the limit)
340 Oct 1, 2018 Resolved No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 21.5 pCi/L, federal limit 5 pCi/L (4.3 times the limit)
340 Oct 1, 2018 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 14.7 pCi/L, federal limit 5 pCi/L (2.9 times the limit)
340 Oct 1, 2018 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 19.25 pCi/L, federal limit 15 pCi/L (1.3 times the limit)
340 Jul 1, 2018 Resolved No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 22.42 pCi/L, federal limit 5 pCi/L (4.5 times the limit)
340 Jul 1, 2018 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 16.33 pCi/L, federal limit 15 pCi/L (1.1 times the limit)
340 Jul 1, 2018 Resolved No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 14.82 pCi/L, federal limit 5 pCi/L (3 times the limit)
340 Jul 1, 2018 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 14.97 pCi/L, federal limit 5 pCi/L (3 times the limit)
340 Apr 1, 2018 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 16 pCi/L, federal limit 15 pCi/L (1.1 times the limit)
340 Apr 1, 2018 Resolved No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 23.33 pCi/L, federal limit 5 pCi/L (4.7 times the limit)
340 Apr 1, 2018 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 16 pCi/L, federal limit 15 pCi/L (1.1 times the limit)
340 Jan 1, 2018 Resolved No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 14.95 pCi/L, federal limit 5 pCi/L (3 times the limit)
340 Jan 1, 2018 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 16 pCi/L, federal limit 15 pCi/L (1.1 times the limit)
340 Jan 1, 2018 Resolved No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 23.35 pCi/L, federal limit 5 pCi/L (4.7 times the limit)
340 Jan 1, 2018 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 14.9 pCi/L, federal limit 5 pCi/L (3 times the limit)
340 Jan 1, 2017 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 18 pCi/L, federal limit 15 pCi/L (1.2 times the limit)
340 Jan 1, 2017 Resolved No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 23.4 pCi/L, federal limit 5 pCi/L (4.7 times the limit)
340 Jan 1, 2017 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 12.3 pCi/L, federal limit 5 pCi/L (2.5 times the limit)
340 Jan 1, 2016 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 19 pCi/L, federal limit 5 pCi/L (3.8 times the limit)
340 Jan 1, 2016 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 19.5 pCi/L, federal limit 15 pCi/L (1.3 times the limit)
340 Jan 1, 2016 Resolved No

Full record since 1994

EPA's records for South Swink Water Authority go back to 1994. Before October 19, 2016 they list 25 health-based violations (8 resolved, 17 archived by EPA without a recorded fix) and no monitoring or reporting violations.

Violations that began in Health-based Monitoring and reporting
1990s 2 0
2000s 4 0
2010 to October 18, 2016 19 0
October 19, 2016 to 2019 32 0
2020s 70 0

Most recent health-based violation before October 19, 2016: Combined Radium (-226 and -228), began January 2016, Archived.

Show all 25 health-based violations before October 19, 2016
Contaminant Start date Status
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 12.3 pCi/L, federal limit 5 pCi/L (2.5 times the limit)
Jan 1, 2016 Archived
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 19 pCi/L, federal limit 5 pCi/L (3.8 times the limit)
Jan 1, 2016 Archived
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 19.5 pCi/L, federal limit 15 pCi/L (1.3 times the limit)
Jan 1, 2016 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 13 pCi/L, federal limit 5 pCi/L (2.6 times the limit)
Jan 1, 2015 Archived
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 20 pCi/L, federal limit 5 pCi/L (4 times the limit)
Jan 1, 2015 Archived
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 20 pCi/L, federal limit 15 pCi/L (1.3 times the limit)
Jan 1, 2015 Resolved
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 42 pCi/L, federal limit 15 pCi/L (2.8 times the limit)
Jan 1, 2014 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 12.3 pCi/L, federal limit 5 pCi/L (2.5 times the limit)
Jan 1, 2014 Archived
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 26 pCi/L, federal limit 15 pCi/L (1.7 times the limit)
Jan 1, 2014 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 11 pCi/L, federal limit 5 pCi/L (2.2 times the limit)
Jan 1, 2014 Archived
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 13 pCi/L, federal limit 5 pCi/L (2.6 times the limit)
Jan 1, 2013 Archived
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 19 pCi/L, federal limit 5 pCi/L (3.8 times the limit)
Jan 1, 2013 Archived
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 18 pCi/L, federal limit 15 pCi/L (1.2 times the limit)
Jan 1, 2013 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 11 pCi/L, federal limit 5 pCi/L (2.2 times the limit)
Jan 1, 2012 Archived
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 12 pCi/L, federal limit 5 pCi/L (2.4 times the limit)
Jan 1, 2012 Archived
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 16 pCi/L, federal limit 5 pCi/L (3.2 times the limit)
Jan 1, 2011 Archived
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 12 pCi/L, federal limit 5 pCi/L (2.4 times the limit)
Jan 1, 2011 Archived
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 14.5 pCi/L, federal limit 5 pCi/L (2.9 times the limit)
Jan 1, 2010 Archived
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 9.5 pCi/L, federal limit 5 pCi/L (1.9 times the limit)
Jan 1, 2010 Archived
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 13 pCi/L, federal limit 5 pCi/L (2.6 times the limit)
Jan 1, 2009 Archived
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 19 pCi/L, federal limit 15 pCi/L (1.3 times the limit)
Jan 1, 2009 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 14 pCi/L, federal limit 5 pCi/L (2.8 times the limit)
Jan 1, 2008 Archived
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 21 pCi/L, federal limit 15 pCi/L (1.4 times the limit)
Jan 1, 2008 Resolved
Combined Radium (-226 and -228)
Contaminant limit exceeded
Measured 7 pCi/L, federal limit 5 pCi/L (1.4 times the limit)
Jan 1, 1994 Archived
Gross Alpha, Excl. Radon and U
Contaminant limit exceeded
Measured 30 pCi/L, federal limit 15 pCi/L (2 times the limit)
Jan 1, 1994 Resolved

Enforcement actions

Colorado regulators took 3 formal enforcement actions against South Swink Water Authority between 2000 and 2022. The most recent was a compliance order (no penalty) in May 2022.

Date By Action Violations covered
May 31, 2022 Colorado Compliance order (no penalty) 127 violations (127 health-based): Gross Alpha, Excl. Radon and U, Combined Radium (-226 and -228)
Jan 4, 2018 Colorado Compliance order (no penalty) 63 violations (63 health-based): Gross Alpha, Excl. Radon and U, Combined Radium (-226 and -228)
Mar 16, 2000 Colorado Compliance order (no penalty) 25 violations (25 health-based): Gross Alpha, Excl. Radon and U, Combined Radium (-226 and -228)

What the violations mean

Combined Radium (-226 and -228)

66 incidents

Test results for Combined Radium (-226 and -228) were above the federal limit (a maximum contaminant level violation).

The utility had to notify customers about each of these violations.

Gross Alpha, Excl. Radon and U

39 incidents

Test results for Gross Alpha, Excl. Radon and U were above the federal limit (a maximum contaminant level violation).

The utility had to notify customers about each of these violations.

Where the water comes from

South Swink Water Authority draws water from 4 wells (1 of them for emergency, seasonal or other part-time use).

Annual water quality report

South Swink Water Authority must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Where the state allows it, systems serving fewer than 10,000 people may publish the report in a local newspaper or news site instead of mailing it, and must provide a copy on request.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water