Public water system record

Lewiston Community Services District

Serves Lewiston, Trinity County, CA · 677 people served

Federal records show 1 health-based violation and 2 monitoring/reporting issues for Lewiston Community Services District in the last ten years. The most serious issue in this window was a resolved Interim Enhanced Surface Water Treatment Rule violation.

  • CA5301002
  • JUNCTION CITY
  • CA
  • 677 served

System profile

Source water Surface water
ZIP 96048
EPA system ID CA5301002

Verify this system on EPA ECHO →

Health-based violations, last 10 years
1
Resolved
1
Unresolved
0
Any acute record
Yes
Monitoring issues, last 10 years
2

Key facts

  • Lewiston Community Services District draws water from 4 wells and 1 infiltration gallery (1 of them for emergency, seasonal or other part-time use).
  • Most recent formal enforcement: compliance order (no penalty) by California, May 2024.
  • Record on file since 1992, with 34 health-based violations before October 19, 2016.
  • Lead pipe inventory: 0 lead and 0 unknown out of 236 service lines.

Check whether Lewiston Community Services District serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

Contaminant Rule family Start date Status Acute
Interim Enhanced Surface Water Treatment Rule
Treatment technique failure
120 Mar 1, 2024 Resolved Yes

Monitoring and reporting issues

Since October 2016

Missed tests or reports, not contaminants found above a limit.

Issue Start date Status
Revised Total Coliform Rule
OTHER
Nov 1, 2020 Resolved
Surface Water Treatment Rule
Monitoring and reporting
Nov 1, 2020 Resolved

Full record since 1992

EPA's records for Lewiston Community Services District go back to 1992. Before October 19, 2016 they list 34 health-based violations (34 resolved) and 1 monitoring or reporting violation.

Violations that began in Health-based Monitoring and reporting
1990s 2 1
2000s 9 0
2010 to October 18, 2016 23 0
2020s 1 2

Most recent health-based violation before October 19, 2016: Arsenic, began April 2015, Resolved.

Show all 34 health-based violations before October 19, 2016
Contaminant Start date Status
Arsenic
Contaminant limit exceeded
Measured 0.0278 mg/L, federal limit 0.01 mg/L (2.8 times the limit)
Apr 1, 2015 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.023 mg/L, federal limit 0.01 mg/L (2.3 times the limit)
Jan 1, 2015 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.0204 mg/L, federal limit 0.01 mg/L (2 times the limit)
Oct 1, 2014 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.0194 mg/L, federal limit 0.01 mg/L (1.9 times the limit)
Jul 1, 2014 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.0194 mg/L, federal limit 0.01 mg/L (1.9 times the limit)
Apr 1, 2014 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.0271 mg/L, federal limit 0.01 mg/L (2.7 times the limit)
Jan 1, 2014 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.0178 mg/L, federal limit 0.01 mg/L (1.8 times the limit)
Oct 1, 2013 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.0186 mg/L, federal limit 0.01 mg/L (1.9 times the limit)
Jul 1, 2013 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.0195 mg/L, federal limit 0.01 mg/L (2 times the limit)
Apr 1, 2013 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.0234 mg/L, federal limit 0.01 mg/L (2.3 times the limit)
Jan 1, 2013 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.0266 mg/L, federal limit 0.01 mg/L (2.7 times the limit)
Oct 1, 2012 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.0272 mg/L, federal limit 0.01 mg/L (2.7 times the limit)
Jul 1, 2012 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.0271 mg/L, federal limit 0.01 mg/L (2.7 times the limit)
Apr 1, 2012 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.0258 mg/L, federal limit 0.01 mg/L (2.6 times the limit)
Jan 1, 2012 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.0243 mg/L, federal limit 0.01 mg/L (2.4 times the limit)
Oct 1, 2011 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.0249 mg/L, federal limit 0.01 mg/L (2.5 times the limit)
Jul 1, 2011 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.0246 mg/L, federal limit 0.01 mg/L (2.5 times the limit)
Apr 1, 2011 Resolved
Surface Water Treatment Rule
Treatment technique failure
Feb 1, 2011 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.0246 mg/L, federal limit 0.01 mg/L (2.5 times the limit)
Jan 1, 2011 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.0261 mg/L, federal limit 0.01 mg/L (2.6 times the limit)
Oct 1, 2010 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.0245 mg/L, federal limit 0.01 mg/L (2.5 times the limit)
Jul 1, 2010 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.0248 mg/L, federal limit 0.01 mg/L (2.5 times the limit)
Apr 1, 2010 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.0231 mg/L, federal limit 0.01 mg/L (2.3 times the limit)
Jan 1, 2010 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.023 mg/L, federal limit 0.01 mg/L (2.3 times the limit)
Oct 1, 2009 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.0243 mg/L, federal limit 0.01 mg/L (2.4 times the limit)
Jul 1, 2009 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.0254 mg/L, federal limit 0.01 mg/L (2.5 times the limit)
Apr 1, 2009 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.03 mg/L, federal limit 0.01 mg/L (3 times the limit)
Jan 1, 2009 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.0304 mg/L, federal limit 0.01 mg/L (3 times the limit)
Oct 1, 2008 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.0278 mg/L, federal limit 0.01 mg/L (2.8 times the limit)
Jul 1, 2008 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.0253 mg/L, federal limit 0.01 mg/L (2.5 times the limit)
Apr 1, 2008 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.0192 mg/L, federal limit 0.01 mg/L (1.9 times the limit)
Jan 1, 2008 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.0135 mg/L, federal limit 0.01 mg/L (1.4 times the limit)
Oct 7, 2007 Resolved
Surface Water Treatment Rule
Treatment technique failure
Jun 1, 1993 Resolved
Surface Water Treatment Rule
Treatment technique failure
Jan 1, 1992 Resolved

Enforcement actions

California regulators took 6 formal enforcement actions against Lewiston Community Services District between 1994 and 2024. The most recent was a compliance order (no penalty) in May 2024.

Date By Action Violations covered
May 28, 2024 California Compliance order (no penalty) 1 violation (1 health-based): Interim Enhanced Surface Water Treatment Rule
Apr 30, 2021 California Compliance order (no penalty) 1 violation: Revised Total Coliform Rule
Jun 22, 2011 California Compliance order (no penalty) 1 violation (1 health-based): Surface Water Treatment Rule
Feb 24, 2009 California Compliance order (no penalty) 31 violations (31 health-based): Arsenic
Jul 18, 1994 California Signed compliance agreement 1 violation (1 health-based): Surface Water Treatment Rule
Jun 28, 1994 California Signed compliance agreement 1 violation (1 health-based): Surface Water Treatment Rule

What the violations mean

Interim Enhanced Surface Water Treatment Rule

1 incident

The system did not meet a filtration or treatment requirement for surface water

Inadequate treatment of surface water can let pathogens such as Cryptosporidium and Giardia through

Where the water comes from

Lewiston Community Services District draws water from 4 wells and 1 infiltration gallery (1 of them for emergency, seasonal or other part-time use).

Annual water quality report

Lewiston Community Services District must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Where the state allows it, systems serving fewer than 10,000 people may publish the report in a local newspaper or news site instead of mailing it, and must provide a copy on request.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water

To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by California.