Public water system record

City of Dos Palos

Serves an area of Merced County, CA that includes Dos Palos and South Dos Palos · 7,452 people served

Federal records show 27 health-based violations and 1 monitoring/reporting issue for City of Dos Palos in the last ten years. The most serious issue in this window was a Total Trihalomethanes (TTHMs) violation that EPA lists as archived, not resolved.

  • CA2410002
  • DOS PALOS
  • CA
  • 7,452 served

System profile

Source water Surface water
ZIP 93620
EPA system ID CA2410002

Verify this system on EPA ECHO →

Health-based violations, last 10 years
27
Resolved
1
Unresolved
0
Archived by EPA
26
Any acute record
No
Monitoring issues, last 10 years
1

Key facts

  • City of Dos Palos draws water from 1 surface water intake.
  • Highest measured level in the last 10 years: Total Trihalomethanes (TTHMs), 143 µg/L, federal limit 80 µg/L (1.8 times the limit), 2021.
  • Most recent formal enforcement: compliance order (no penalty) by California, February 2023.
  • Record on file since 1983, with 17 health-based violations before October 19, 2016.
  • Lead pipe inventory: 0 lead and 0 unknown out of 2,738 service lines.

Check whether City of Dos Palos serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

Contaminant Rule family Start date Status Acute
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.0892 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
220 Jul 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.0878 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
220 Apr 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.0931 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
220 Jan 1, 2025 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.0984 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
220 Oct 1, 2024 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.1036 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
220 Apr 1, 2024 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.084 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
220 Apr 1, 2023 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.107 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
220 Jan 1, 2023 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
220 Oct 1, 2022 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 143 µg/L, federal limit 80 µg/L (1.8 times the limit)
220 Jul 1, 2021 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 120 µg/L, federal limit 80 µg/L (1.5 times the limit)
220 Apr 1, 2021 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 98 µg/L, federal limit 60 µg/L (1.6 times the limit)
220 Jan 1, 2021 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 108 µg/L, federal limit 80 µg/L (1.4 times the limit)
220 Jan 1, 2021 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
CARBON, TOTAL
Treatment technique failure
210 Oct 1, 2020 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 106 µg/L, federal limit 80 µg/L (1.3 times the limit)
220 Oct 1, 2020 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
CARBON, TOTAL
Treatment technique failure
210 Jul 1, 2020 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 93.4 µg/L, federal limit 80 µg/L (1.2 times the limit)
220 Jul 1, 2020 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
CARBON, TOTAL
Treatment technique failure
210 Apr 1, 2020 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.091 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
220 Apr 1, 2020 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.11 mg/L, federal limit 0.08 mg/L (1.4 times the limit)
220 Oct 1, 2019 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.089 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
220 Apr 1, 2019 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.105 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
220 Jan 1, 2019 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.104 mg/L, federal limit 0.08 mg/L (1.3 times the limit)
220 Oct 1, 2018 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.094 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
220 Jul 1, 2018 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 97 µg/L, federal limit 80 µg/L (1.2 times the limit)
220 Apr 1, 2017 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Surface Water Treatment Rule
Treatment technique failure
120 Jan 1, 2017 Resolved No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.122 mg/L, federal limit 0.08 mg/L (1.5 times the limit)
220 Jan 1, 2017 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 125 µg/L, federal limit 80 µg/L (1.6 times the limit)
220 Oct 1, 2016 Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
No

Monitoring and reporting issues

Since October 2016

Missed tests or reports, not contaminants found above a limit.

Issue Start date Status
Lead and Copper Rule
Monitoring and reporting
Oct 1, 2022 Active
Enforcement action in place

Full record since 1983

EPA's records for City of Dos Palos go back to 1983. Before October 19, 2016 they list 17 health-based violations (3 resolved, 14 archived by EPA without a recorded fix) and 2 monitoring or reporting violations.

Violations that began in Health-based Monitoring and reporting
1980s 0 1
2000s 3 1
2010 to October 18, 2016 14 0
October 19, 2016 to 2019 8 0
2020s 18 1

Most recent health-based violation before October 19, 2016: Total Trihalomethanes (TTHMs), began October 2016, Archived.

Show all 17 health-based violations before October 19, 2016
Contaminant Start date Status
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 125 µg/L, federal limit 80 µg/L (1.6 times the limit)
Oct 1, 2016 Archived
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 132 µg/L, federal limit 80 µg/L (1.7 times the limit)
Jul 1, 2016 Archived
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 150 µg/L, federal limit 80 µg/L (1.9 times the limit)
Apr 1, 2016 Archived
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 147 µg/L, federal limit 80 µg/L (1.8 times the limit)
Jan 1, 2016 Archived
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 145 µg/L, federal limit 80 µg/L (1.8 times the limit)
Oct 1, 2015 Archived
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 135 µg/L, federal limit 80 µg/L (1.7 times the limit)
Jul 1, 2015 Archived
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Apr 1, 2015 Archived
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 135 µg/L, federal limit 80 µg/L (1.7 times the limit)
Jan 1, 2015 Archived
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 135 µg/L, federal limit 80 µg/L (1.7 times the limit)
Oct 1, 2014 Archived
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.155 mg/L, federal limit 0.08 mg/L (1.9 times the limit)
Jul 1, 2014 Archived
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.125 mg/L, federal limit 0.08 mg/L (1.6 times the limit)
Apr 1, 2014 Archived
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.0873 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
Jul 1, 2013 Archived
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.0858 mg/L, federal limit 0.08 mg/L (1.1 times the limit)
Apr 1, 2013 Archived
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.0925 mg/L, federal limit 0.08 mg/L (1.2 times the limit)
Jan 1, 2013 Archived
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.0828 mg/L, federal limit 0.08 mg/L (at or just above the limit)
Oct 1, 2007 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 0.0833 mg/L, federal limit 0.08 mg/L (at or just above the limit)
Jul 1, 2007 Resolved
Surface Water Treatment Rule
Treatment technique failure
Apr 1, 2004 Resolved

Enforcement actions

California regulators took 8 formal enforcement actions against City of Dos Palos between 2004 and 2023. The most recent was a compliance order (no penalty) in February 2023.

Date By Action Violations covered
Feb 2, 2023 California Compliance order (no penalty) 1 violation: Lead and Copper Rule
Mar 19, 2021 California Compliance order (no penalty) 3 violations (3 health-based): CARBON, TOTAL
Nov 12, 2020 California Compliance order (no penalty) 16 violations (16 health-based): Total Trihalomethanes (TTHMs), Haloacetic Acids (HAA5)
Aug 29, 2017 California Compliance order (no penalty) 1 violation (1 health-based): Surface Water Treatment Rule
Dec 30, 2014 California Compliance order (no penalty) 16 violations (16 health-based): Total Trihalomethanes (TTHMs)
May 17, 2013 California Compliance order (no penalty) 4 violations (4 health-based): Total Trihalomethanes (TTHMs)
Sep 26, 2007 California Compliance order (no penalty) 2 violations (2 health-based): Total Trihalomethanes (TTHMs)
Sep 22, 2004 California Compliance order (no penalty) 1 violation (1 health-based): Surface Water Treatment Rule

What the violations mean

Total Trihalomethanes (TTHMs)

22 incidents

Disinfection byproduct levels exceeded the federal limit

Long-term TTHM exposure may increase bladder cancer risk

CARBON, TOTAL

3 incidents

The system did not complete a treatment step or action that federal rules require for CARBON, TOTAL (a treatment technique violation).

The utility had to notify customers about each of these violations.

Haloacetic Acids (HAA5)

1 incident

Haloacetic acid byproducts exceeded the federal limit

Long-term exposure to HAAs may increase cancer risk

Surface Water Treatment Rule

1 incident

The system did not complete a treatment step or action that the Surface Water Treatment Rule requires (a treatment technique violation).

The utility had to notify customers about this violation.

Where the water comes from

City of Dos Palos draws water from 1 surface water intake.

Annual water quality report

City of Dos Palos must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Where the state allows it, systems serving fewer than 10,000 people may publish the report in a local newspaper or news site instead of mailing it, and must provide a copy on request.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water

To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by California.