Public water system record
Cedar Valley Mutual Water Co
Serves Oakhurst, Madera County, CA · 137 people served
Federal records show 29 health-based violations and 3 monitoring/reporting issues for Cedar Valley Mutual Water Co in the last ten years, including an unresolved LEAD AND COPPER RULE REVISIONS violation.
System profile
- Health-based violations, last 10 years
- 29
- Resolved
- 0
- Unresolved
- 1
- Archived by EPA
- 28
- Any acute record
- No
- Monitoring issues, last 10 years
- 3
Key facts
- Cedar Valley Mutual Water Co draws water from 1 spring.
- Highest measured level in the last 10 years: Arsenic, 0.022053 mg/L, federal limit 0.01 mg/L (2.2 times the limit), 2021.
- Most recent formal enforcement: compliance order (no penalty) by California, June 2015.
- Record on file since 1980, with 30 health-based violations before October 19, 2016.
Check whether Cedar Valley Mutual Water Co serves your address
Health-based violations
Since October 2016Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.
| Contaminant | Rule family | Start date | Status | Acute |
|---|---|---|---|---|
|
Arsenic
Contaminant limit exceeded
Measured 0.0192 mg/L, federal limit 0.01 mg/L (1.9 times the limit)
|
330 | Oct 1, 2025 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.019 mg/L, federal limit 0.01 mg/L (1.9 times the limit)
|
330 | Jul 1, 2025 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.019 mg/L, federal limit 0.01 mg/L (1.9 times the limit)
|
330 | Apr 1, 2025 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.019 mg/L, federal limit 0.01 mg/L (1.9 times the limit)
|
330 | Jan 1, 2025 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
LEAD AND COPPER RULE REVISIONS
Treatment technique failure
|
350 | Oct 17, 2024 | Active | No |
|
Arsenic
Contaminant limit exceeded
Measured 0.019 mg/L, federal limit 0.01 mg/L (1.9 times the limit)
|
330 | Oct 1, 2024 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.019 mg/L, federal limit 0.01 mg/L (1.9 times the limit)
|
330 | Jul 1, 2024 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.018 mg/L, federal limit 0.01 mg/L (1.8 times the limit)
|
330 | Apr 1, 2024 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.019 mg/L, federal limit 0.01 mg/L (1.9 times the limit)
|
330 | Jan 1, 2024 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.0167 mg/L, federal limit 0.01 mg/L (1.7 times the limit)
|
330 | Oct 1, 2022 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.0161 mg/L, federal limit 0.01 mg/L (1.6 times the limit)
|
330 | Jul 1, 2022 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.0172 mg/L, federal limit 0.01 mg/L (1.7 times the limit)
|
330 | Apr 1, 2022 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.0173 mg/L, federal limit 0.01 mg/L (1.7 times the limit)
|
330 | Jan 1, 2022 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.01975 mg/L, federal limit 0.01 mg/L (2 times the limit)
|
330 | Oct 1, 2021 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.021975 mg/L, federal limit 0.01 mg/L (2.2 times the limit)
|
330 | Jul 1, 2021 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.022053 mg/L, federal limit 0.01 mg/L (2.2 times the limit)
|
330 | Apr 1, 2021 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.02061 mg/L, federal limit 0.01 mg/L (2.1 times the limit)
|
330 | Jan 1, 2021 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.020903 mg/L, federal limit 0.01 mg/L (2.1 times the limit)
|
330 | Oct 1, 2020 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.020445 mg/L, federal limit 0.01 mg/L (2 times the limit)
|
330 | Jul 1, 2020 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.020433 mg/L, federal limit 0.01 mg/L (2 times the limit)
|
330 | Apr 1, 2020 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.021618 mg/L, federal limit 0.01 mg/L (2.2 times the limit)
|
330 | Jan 1, 2020 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.021195 mg/L, federal limit 0.01 mg/L (2.1 times the limit)
|
330 | Oct 1, 2019 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.0208 mg/L, federal limit 0.01 mg/L (2.1 times the limit)
|
330 | Jul 1, 2019 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.019623 mg/L, federal limit 0.01 mg/L (2 times the limit)
|
330 | Apr 1, 2019 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.02071 mg/L, federal limit 0.01 mg/L (2.1 times the limit)
|
330 | Jan 1, 2019 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.02004 mg/L, federal limit 0.01 mg/L (2 times the limit)
|
330 | Jan 1, 2018 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.021583 mg/L, federal limit 0.01 mg/L (2.2 times the limit)
|
330 | Oct 1, 2017 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.022 mg/L, federal limit 0.01 mg/L (2.2 times the limit)
|
330 | Jan 1, 2017 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
|
Arsenic
Contaminant limit exceeded
Measured 0.0209 mg/L, federal limit 0.01 mg/L (2.1 times the limit)
|
330 | Jan 1, 2016 |
Archived
Violation period ended. EPA no longer counts it toward current compliance, but no fix was formally recorded.
|
No |
Monitoring and reporting issues
Since October 2016Missed tests or reports, not contaminants found above a limit.
| Issue | Start date | Status |
|---|---|---|
|
LEAD AND COPPER RULE REVISIONS
RPT
|
Oct 17, 2024 | Active |
|
Arsenic
Monitoring and reporting
|
Jul 1, 2017 | Resolved |
|
Arsenic
Monitoring and reporting
|
Apr 1, 2017 | Resolved |
Full record since 1980
EPA's records for Cedar Valley Mutual Water Co go back to 1980. Before October 19, 2016 they list 30 health-based violations (1 resolved, 29 archived by EPA without a recorded fix) and 4 monitoring or reporting violations.
| Violations that began in | Health-based | Monitoring and reporting |
|---|---|---|
| 1980s | 0 | 3 |
| 1990s | 0 | 1 |
| 2000s | 5 | 0 |
| 2010 to October 18, 2016 | 25 | 0 |
| October 19, 2016 to 2019 | 7 | 2 |
| 2020s | 21 | 1 |
Most recent health-based violation before October 19, 2016: Arsenic, began July 2016, Archived.
Show all 30 health-based violations before October 19, 2016
| Contaminant | Start date | Status |
|---|---|---|
|
Arsenic
Contaminant limit exceeded
Measured 0.017 mg/L, federal limit 0.01 mg/L (1.7 times the limit)
|
Jul 1, 2016 | Archived |
|
Arsenic
Contaminant limit exceeded
Measured 0.0209 mg/L, federal limit 0.01 mg/L (2.1 times the limit)
|
Jan 1, 2016 | Archived |
|
Arsenic
Contaminant limit exceeded
Measured 0.017 mg/L, federal limit 0.01 mg/L (1.7 times the limit)
|
Jul 1, 2015 | Archived |
|
Arsenic
Contaminant limit exceeded
Measured 0.01816 mg/L, federal limit 0.01 mg/L (1.8 times the limit)
|
Jan 1, 2015 | Archived |
|
Total Coliform (acute)
Contaminant limit exceeded
|
Nov 1, 2014 | Resolved |
|
Arsenic
Contaminant limit exceeded
|
Oct 1, 2014 | Archived |
|
Arsenic
Contaminant limit exceeded
Measured 0.019 mg/L, federal limit 0.01 mg/L (1.9 times the limit)
|
Jul 1, 2014 | Archived |
|
Arsenic
Contaminant limit exceeded
Measured 0.026 mg/L, federal limit 0.01 mg/L (2.6 times the limit)
|
Apr 1, 2014 | Archived |
|
Arsenic
Contaminant limit exceeded
Measured 0.017 mg/L, federal limit 0.01 mg/L (1.7 times the limit)
|
Jan 1, 2014 | Archived |
|
Arsenic
Contaminant limit exceeded
Measured 0.017 mg/L, federal limit 0.01 mg/L (1.7 times the limit)
|
Oct 1, 2013 | Archived |
|
Arsenic
Contaminant limit exceeded
Measured 0.017 mg/L, federal limit 0.01 mg/L (1.7 times the limit)
|
Jul 1, 2013 | Archived |
|
Arsenic
Contaminant limit exceeded
Measured 0.017 mg/L, federal limit 0.01 mg/L (1.7 times the limit)
|
Apr 1, 2013 | Archived |
|
Arsenic
Contaminant limit exceeded
Measured 0.017 mg/L, federal limit 0.01 mg/L (1.7 times the limit)
|
Jan 1, 2013 | Archived |
|
Arsenic
Contaminant limit exceeded
Measured 0.017 mg/L, federal limit 0.01 mg/L (1.7 times the limit)
|
Oct 1, 2012 | Archived |
|
Arsenic
Contaminant limit exceeded
Measured 0.017 mg/L, federal limit 0.01 mg/L (1.7 times the limit)
|
Jul 1, 2012 | Archived |
|
Arsenic
Contaminant limit exceeded
Measured 0.017 mg/L, federal limit 0.01 mg/L (1.7 times the limit)
|
Apr 1, 2012 | Archived |
|
Arsenic
Contaminant limit exceeded
Measured 0.017 mg/L, federal limit 0.01 mg/L (1.7 times the limit)
|
Jan 10, 2012 | Archived |
|
Arsenic
Contaminant limit exceeded
Measured 0.017 mg/L, federal limit 0.01 mg/L (1.7 times the limit)
|
Oct 1, 2011 | Archived |
|
Arsenic
Contaminant limit exceeded
Measured 0.019 mg/L, federal limit 0.01 mg/L (1.9 times the limit)
|
Jul 1, 2011 | Archived |
|
Arsenic
Contaminant limit exceeded
Measured 0.023 mg/L, federal limit 0.01 mg/L (2.3 times the limit)
|
Apr 1, 2011 | Archived |
|
Arsenic
Contaminant limit exceeded
Measured 0.023 mg/L, federal limit 0.01 mg/L (2.3 times the limit)
|
Jan 1, 2011 | Archived |
|
Arsenic
Contaminant limit exceeded
Measured 0.023 mg/L, federal limit 0.01 mg/L (2.3 times the limit)
|
Oct 1, 2010 | Archived |
|
Arsenic
Contaminant limit exceeded
Measured 0.023 mg/L, federal limit 0.01 mg/L (2.3 times the limit)
|
Jul 1, 2010 | Archived |
|
Arsenic
Contaminant limit exceeded
Measured 0.023 mg/L, federal limit 0.01 mg/L (2.3 times the limit)
|
Apr 1, 2010 | Archived |
|
Arsenic
Contaminant limit exceeded
Measured 0.023 mg/L, federal limit 0.01 mg/L (2.3 times the limit)
|
Jan 1, 2010 | Archived |
|
Arsenic
Contaminant limit exceeded
Measured 0.018 mg/L, federal limit 0.01 mg/L (1.8 times the limit)
|
Oct 1, 2009 | Archived |
|
Arsenic
Contaminant limit exceeded
Measured 0.015 mg/L, federal limit 0.01 mg/L (1.5 times the limit)
|
Jul 1, 2009 | Archived |
|
Arsenic
Contaminant limit exceeded
Measured 0.015 mg/L, federal limit 0.01 mg/L (1.5 times the limit)
|
Apr 1, 2009 | Archived |
|
Arsenic
Contaminant limit exceeded
Measured 0.015 mg/L, federal limit 0.01 mg/L (1.5 times the limit)
|
Jan 1, 2009 | Archived |
|
Arsenic
Contaminant limit exceeded
Measured 0.015 mg/L, federal limit 0.01 mg/L (1.5 times the limit)
|
Oct 1, 2007 | Archived |
Enforcement actions
California regulators took 2 formal enforcement actions against Cedar Valley Mutual Water Co between 2014 and 2015. The most recent was a compliance order (no penalty) in June 2015.
| Date | By | Action | Violations covered |
|---|---|---|---|
| Jun 15, 2015 | California | Compliance order (no penalty) | 35 violations (35 health-based): Arsenic |
| Aug 12, 2014 | California | Compliance order (no penalty) | 26 violations (26 health-based): Arsenic |
What the violations mean
Arsenic
28 incidentsArsenic exceeded the federal limit
Long-term arsenic exposure is linked to cancer and cardiovascular effects
LEAD AND COPPER RULE REVISIONS
1 incidentThe system did not complete a treatment step or action that the LEAD AND COPPER RULE REVISIONS requires (a treatment technique violation).
The utility had to notify customers about this violation.
Where the water comes from
Cedar Valley Mutual Water Co draws water from 1 spring.
Annual water quality report
Cedar Valley Mutual Water Co must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.
Systems serving 500 or fewer people may meet the rule by telling customers the report is available on request, so you may need to ask Cedar Valley Mutual Water Co for a copy.
Find a posted report with EPA's Consumer Confidence Report search
Testing your own water
To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by California.
Certified drinking water labs by state EPA guidance for private wells