Public water system record

Charles Brown Water Company

Serves Shoshone, Inyo County, CA · 242 people served

Federal records show 2 health-based violations and 7 monitoring/reporting issues for Charles Brown Water Company in the last ten years, including an unresolved LEAD AND COPPER RULE REVISIONS violation.

  • CA1400004
  • SHOSHONE
  • CA
  • 242 served

System profile

Source water Groundwater
ZIP 92384
EPA system ID CA1400004

Verify this system on EPA ECHO →

Health-based violations, last 10 years
2
Resolved
1
Unresolved
1
Any acute record
No
Monitoring issues, last 10 years
7

Key facts

  • Charles Brown Water Company draws water from 1 spring.
  • Most recent formal enforcement: compliance order (no penalty) by California, December 2024.
  • Record on file since 1979, with 15 health-based violations before October 19, 2016.

Check whether Charles Brown Water Company serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

Contaminant Rule family Start date Status Acute
LEAD AND COPPER RULE REVISIONS
Treatment technique failure
350 Oct 17, 2024 Active No
Revised Total Coliform Rule
Treatment technique failure
110 Jul 1, 2023 Resolved No

Monitoring and reporting issues

Since October 2016

Missed tests or reports, not contaminants found above a limit.

Issue Start date Status
LEAD AND COPPER RULE REVISIONS
RPT
Oct 17, 2024 Active
Lead and Copper Rule
Monitoring and reporting
Jun 1, 2024 Active
Enforcement action in place
Revised Total Coliform Rule
Monitoring violation
Jul 1, 2023 Resolved
Revised Total Coliform Rule
Monitoring violation
Jun 1, 2023 Resolved
Groundwater Rule
Monitoring and reporting
Jun 1, 2023 Resolved
Lead and Copper Rule
Monitoring and reporting
Jun 1, 2020 Resolved
Nitrate
Monitoring and reporting
Jan 1, 2017 Resolved

Full record since 1979

EPA's records for Charles Brown Water Company go back to 1979. Before October 19, 2016 they list 15 health-based violations (4 resolved, 11 archived by EPA without a recorded fix) and 24 monitoring or reporting violations.

Violations that began in Health-based Monitoring and reporting
1970s 2 1
1980s 6 3
1990s 1 1
2000s 3 16
2010 to October 18, 2016 3 3
October 19, 2016 to 2019 0 1
2020s 2 6

Most recent health-based violation before October 19, 2016: Arsenic, began July 2011, Resolved.

Show all 15 health-based violations before October 19, 2016
Contaminant Start date Status
Arsenic
Contaminant limit exceeded
Measured 0.012 mg/L, federal limit 0.01 mg/L (1.2 times the limit)
Jul 1, 2011 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.011 mg/L, federal limit 0.01 mg/L (1.1 times the limit)
Apr 1, 2011 Resolved
Arsenic
Contaminant limit exceeded
Measured 0.011 mg/L, federal limit 0.01 mg/L (1.1 times the limit)
Jan 1, 2011 Resolved
Total Coliform
Contaminant limit exceeded
Oct 1, 2002 Resolved
Total Coliform
Contaminant limit exceeded
Jun 1, 2002 Archived
Total Coliform
Contaminant limit exceeded
May 1, 2002 Archived
Total Coliform
Contaminant limit exceeded
Oct 1, 1996 Archived
Arsenic
Contaminant limit exceeded
Jun 1, 1983 Archived
Arsenic
Contaminant limit exceeded
Mar 28, 1982 Archived
Nitrate (acute)
Contaminant limit exceeded
Mar 28, 1982 Archived
Fluoride
Contaminant limit exceeded
Mar 28, 1982 Archived
Fluoride
Contaminant limit exceeded
Dec 11, 1981 Archived
Arsenic
Contaminant limit exceeded
Dec 11, 1981 Archived
Fluoride
Contaminant limit exceeded
Oct 30, 1979 Archived
Arsenic
Contaminant limit exceeded
Oct 30, 1979 Archived

Enforcement actions

California regulators took 6 formal enforcement actions against Charles Brown Water Company between 2011 and 2024. The most recent was a compliance order (no penalty) in December 2024.

Date By Action Violations covered
Dec 2, 2024 California Compliance order (no penalty) 1 violation: Lead and Copper Rule
Jan 3, 2024 California Compliance order (no penalty) 4 violations (1 health-based): Revised Total Coliform Rule, Groundwater Rule
Dec 17, 2020 California Compliance order (no penalty) 1 violation: Lead and Copper Rule
Apr 16, 2019 California Compliance order (no penalty) 1 violation: Nitrate
Apr 30, 2016 California Compliance order (no penalty) 1 violation: Arsenic
Sep 29, 2011 California Compliance order (no penalty) 3 violations (3 health-based): Arsenic

What the violations mean

LEAD AND COPPER RULE REVISIONS

1 incident

The system did not complete a treatment step or action that the LEAD AND COPPER RULE REVISIONS requires (a treatment technique violation).

The utility had to notify customers about this violation.

Revised Total Coliform Rule

1 incident

The system did not meet a requirement of the Revised Total Coliform Rule

Coliform and E. coli rules protect against bacteria in the distribution system

Where the water comes from

Charles Brown Water Company draws water from 1 spring.

Annual water quality report

Charles Brown Water Company must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Systems serving 500 or fewer people may meet the rule by telling customers the report is available on request, so you may need to ask Charles Brown Water Company for a copy.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water

To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by California.