Public water system record
New London Water Association
Serves an area of Union County, AR · 850 people served
Federal records show 22 health-based violations and 20 monitoring/reporting issues for New London Water Association in the last ten years. The most serious issue in this window was a resolved Total Trihalomethanes (TTHMs) violation.
System profile
- Health-based violations, last 10 years
- 22
- Resolved
- 22
- Unresolved
- 0
- Any acute record
- No
- Monitoring issues, last 10 years
- 20
Key facts
- New London Water Association draws water from 2 wells.
- Highest measured level in the last 10 years: Haloacetic Acids (HAA5), 142 µg/L, federal limit 60 µg/L (2.4 times the limit), 2017.
- Most recent formal enforcement: administrative penalty by Arkansas, November 2022.
- Record on file since 2006, with 21 health-based violations before October 19, 2016.
Check whether New London Water Association serves your address
Health-based violations
Since October 2016Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.
| Contaminant | Rule family | Start date | Status | Acute |
|---|---|---|---|---|
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 104 µg/L, federal limit 80 µg/L (1.3 times the limit)
|
220 | Oct 1, 2022 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 111 µg/L, federal limit 80 µg/L (1.4 times the limit)
|
220 | Oct 1, 2022 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 138 µg/L, federal limit 80 µg/L (1.7 times the limit)
|
220 | Jul 1, 2022 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 146 µg/L, federal limit 80 µg/L (1.8 times the limit)
|
220 | Jul 1, 2022 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 149 µg/L, federal limit 80 µg/L (1.9 times the limit)
|
220 | Apr 1, 2022 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 150 µg/L, federal limit 80 µg/L (1.9 times the limit)
|
220 | Apr 1, 2022 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 106 µg/L, federal limit 80 µg/L (1.3 times the limit)
|
220 | Jan 1, 2022 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 105 µg/L, federal limit 80 µg/L (1.3 times the limit)
|
220 | Jan 1, 2022 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 98 µg/L, federal limit 80 µg/L (1.2 times the limit)
|
220 | Apr 1, 2020 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 113 µg/L, federal limit 80 µg/L (1.4 times the limit)
|
220 | Jan 1, 2020 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 102 µg/L, federal limit 80 µg/L (1.3 times the limit)
|
220 | Oct 1, 2019 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 145 µg/L, federal limit 80 µg/L (1.8 times the limit)
|
220 | Oct 1, 2019 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 109 µg/L, federal limit 80 µg/L (1.4 times the limit)
|
220 | Jul 1, 2019 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 92 µg/L, federal limit 80 µg/L (1.2 times the limit)
|
220 | Apr 1, 2019 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 93 µg/L, federal limit 80 µg/L (1.2 times the limit)
|
220 | Apr 1, 2019 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 106 µg/L, federal limit 80 µg/L (1.3 times the limit)
|
220 | Jan 1, 2019 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 89 µg/L, federal limit 80 µg/L (1.1 times the limit)
|
220 | Oct 1, 2018 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 94 µg/L, federal limit 80 µg/L (1.2 times the limit)
|
220 | Apr 1, 2018 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 105 µg/L, federal limit 80 µg/L (1.3 times the limit)
|
220 | Jul 1, 2017 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 113 µg/L, federal limit 80 µg/L (1.4 times the limit)
|
220 | Apr 1, 2017 | Resolved | No |
|
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 142 µg/L, federal limit 60 µg/L (2.4 times the limit)
|
220 | Jan 1, 2017 | Resolved | No |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 136 µg/L, federal limit 80 µg/L (1.7 times the limit)
|
220 | Oct 1, 2016 | Resolved | No |
Monitoring and reporting issues
Since October 2016Missed tests or reports, not contaminants found above a limit.
| Issue | Start date | Status |
|---|---|---|
|
Consumer Confidence Rule
OTHER
|
Jul 1, 2025 | Active |
|
Public Notice
OTHER
|
Dec 1, 2022 | Resolved |
|
Public Notice
OTHER
|
Jun 1, 2022 | Resolved |
|
Consumer Confidence Rule
OTHER
|
Jul 1, 2020 | Resolved |
|
Public Notice
OTHER
|
Jun 1, 2020 | Resolved |
|
Public Notice
OTHER
|
Dec 1, 2019 | Resolved |
|
Consumer Confidence Rule
OTHER
|
Jul 1, 2019 | Resolved |
|
Public Notice
OTHER
|
Jun 1, 2019 | Resolved |
|
Public Notice
OTHER
|
Mar 1, 2019 | Resolved |
|
Public Notice
OTHER
|
Sep 1, 2018 | Resolved |
|
Consumer Confidence Rule
OTHER
|
Jul 1, 2018 | Resolved |
|
Public Notice
OTHER
|
Apr 1, 2018 | Resolved |
|
Public Notice
OTHER
|
Dec 1, 2017 | Resolved |
|
Public Notice
OTHER
|
Sep 1, 2017 | Resolved |
|
Consumer Confidence Rule
OTHER
|
Jul 1, 2017 | Resolved |
|
Public Notice
OTHER
|
Jun 1, 2017 | Resolved |
|
Revised Total Coliform Rule
Monitoring violation
|
Jun 1, 2017 | Resolved |
|
Public Notice
OTHER
|
Dec 1, 2016 | Resolved |
|
Consumer Confidence Rule
OTHER
|
Jul 1, 2016 | Resolved |
|
Public Notice
OTHER
|
Jun 1, 2015 | Resolved |
Full record since 2006
EPA's records for New London Water Association go back to 2006. Before October 19, 2016 they list 21 health-based violations (21 resolved) and 8 monitoring or reporting violations.
| Violations that began in | Health-based | Monitoring and reporting |
|---|---|---|
| 2000s | 12 | 1 |
| 2010 to October 18, 2016 | 9 | 7 |
| October 19, 2016 to 2019 | 11 | 13 |
| 2020s | 10 | 5 |
Most recent health-based violation before October 19, 2016: Total Trihalomethanes (TTHMs), began October 2016, Resolved.
Show all 21 health-based violations before October 19, 2016
| Contaminant | Start date | Status |
|---|---|---|
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 136 µg/L, federal limit 80 µg/L (1.7 times the limit)
|
Oct 1, 2016 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 88 µg/L, federal limit 80 µg/L (1.1 times the limit)
|
Jul 1, 2016 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 95 µg/L, federal limit 80 µg/L (1.2 times the limit)
|
Jan 1, 2015 | Resolved |
|
Total Coliform
Contaminant limit exceeded
|
Nov 1, 2014 | Resolved |
|
Total Coliform
Contaminant limit exceeded
|
Aug 1, 2014 | Resolved |
|
Total Coliform
Contaminant limit exceeded
|
Mar 1, 2014 | Resolved |
|
Total Coliform
Contaminant limit exceeded
|
Nov 1, 2013 | Resolved |
|
Total Coliform (acute)
Contaminant limit exceeded
|
Jan 1, 2012 | Resolved |
|
Total Coliform
Contaminant limit exceeded
|
Sep 1, 2010 | Resolved |
|
Total Coliform
Contaminant limit exceeded
|
Sep 1, 2009 | Resolved |
|
Total Coliform
Contaminant limit exceeded
|
May 1, 2009 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
|
Jan 1, 2009 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
|
Oct 1, 2008 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 116 µg/L, federal limit 80 µg/L (1.5 times the limit)
|
Jul 1, 2008 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 116 µg/L, federal limit 80 µg/L (1.5 times the limit)
|
Apr 1, 2008 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
|
Jan 1, 2008 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
|
Jul 1, 2007 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
|
Apr 1, 2007 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
|
Jan 1, 2007 | Resolved |
|
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
|
Oct 1, 2006 | Resolved |
|
Total Coliform
Contaminant limit exceeded
|
Mar 1, 2006 | Resolved |
Enforcement actions
Arkansas regulators took 7 formal enforcement actions against New London Water Association between 2008 and 2022. The most recent was an administrative penalty in November 2022.
| Date | By | Action | Violations covered |
|---|---|---|---|
| Nov 28, 2022 | Arkansas | Administrative penalty | 10 violations (8 health-based): Total Trihalomethanes (TTHMs), Public Notice |
| Aug 24, 2022 | Arkansas | Compliance order (no penalty) | 5 violations (4 health-based): Total Trihalomethanes (TTHMs), Public Notice |
| Feb 2, 2017 | Arkansas | Administrative penalty | 28 violations (15 health-based): Total Trihalomethanes (TTHMs), Haloacetic Acids (HAA5), Revised Total Coliform Rule, Public Notice, Consumer Confidence Rule |
| Dec 9, 2016 | Arkansas | Compliance order (no penalty) | 2 violations (1 health-based): Total Trihalomethanes (TTHMs), Consumer Confidence Rule |
| Oct 8, 2014 | Arkansas | Compliance order (no penalty) | 5 violations (3 health-based): Total Coliform, Public Notice |
| Oct 17, 2008 | Arkansas | Compliance order (no penalty) | 6 violations (6 health-based): Total Trihalomethanes (TTHMs) |
| Jul 10, 2008 | Arkansas | Compliance order (no penalty) | 5 violations (5 health-based): Total Trihalomethanes (TTHMs) |
What the violations mean
Total Trihalomethanes (TTHMs)
21 incidentsDisinfection byproduct levels exceeded the federal limit
Long-term TTHM exposure may increase bladder cancer risk
Haloacetic Acids (HAA5)
1 incidentHaloacetic acid byproducts exceeded the federal limit
Long-term exposure to HAAs may increase cancer risk
Where the water comes from
New London Water Association draws water from 2 wells.
Annual water quality report
New London Water Association must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.
Where the state allows it, systems serving fewer than 10,000 people may publish the report in a local newspaper or news site instead of mailing it, and must provide a copy on request.
Find a posted report with EPA's Consumer Confidence Report search
Testing your own water
To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Arkansas.
Certified drinking water labs by state EPA guidance for private wells