Public water system record

Waldron Waterworks

Serves an area of Scott County, AR that includes Waldron · 3,550 people served

Federal records show 1 health-based violation and no monitoring/reporting issues for Waldron Waterworks in the last ten years. The most serious issue in this window was a resolved Stage 1 Disinfection Byproducts Rule violation.

  • AR0000498
  • WALDRON
  • AR
  • 3,550 served

System profile

Source water Surface water
ZIP 72958
EPA system ID AR0000498

Verify this system on EPA ECHO →

Health-based violations, last 10 years
1
Resolved
1
Unresolved
0
Any acute record
No
Monitoring issues, last 10 years
0

Key facts

  • Waldron Waterworks draws water from 2 surface water intakes.
  • Most recent formal enforcement: consent decree or court judgment by Arkansas, August 2009.
  • Record on file since 1994, with 38 health-based violations before October 19, 2016.
  • Lead pipe inventory: 0 lead and 2,100 unknown out of 2,100 service lines.

Check whether Waldron Waterworks serves your address

Address suggestions by Mapbox

Health-based violations

Since October 2016

Violation data reflects EPA records through March 2026. For the most current status, visit the EPA ECHO database.

Contaminant Rule family Start date Status Acute
Stage 1 Disinfection Byproducts Rule
Treatment technique failure
210 Oct 1, 2003 Resolved No

Full record since 1994

EPA's records for Waldron Waterworks go back to 1994. Before October 19, 2016 they list 38 health-based violations (26 resolved, 12 archived by EPA without a recorded fix) and 5 monitoring or reporting violations.

Violations that began in Health-based Monitoring and reporting
1990s 7 5
2000s 16 0
2010 to October 18, 2016 15 0

Most recent health-based violation before October 19, 2016: Total Coliform, began July 2014, Resolved.

Show all 38 health-based violations before October 19, 2016
Contaminant Start date Status
Total Coliform
Contaminant limit exceeded
Jul 1, 2014 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 89 µg/L, federal limit 80 µg/L (1.1 times the limit)
Apr 1, 2012 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 70 µg/L, federal limit 60 µg/L (1.2 times the limit)
Jan 1, 2012 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 108 µg/L, federal limit 80 µg/L (1.4 times the limit)
Jan 1, 2012 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 76 µg/L, federal limit 60 µg/L (1.3 times the limit)
Oct 1, 2011 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 120 µg/L, federal limit 80 µg/L (1.5 times the limit)
Oct 1, 2011 Resolved
Surface Water Treatment Rule
Treatment technique failure
Oct 1, 2011 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 116 µg/L, federal limit 80 µg/L (1.5 times the limit)
Jul 1, 2011 Resolved
Total Coliform
Contaminant limit exceeded
May 1, 2011 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 109 µg/L, federal limit 80 µg/L (1.4 times the limit)
Apr 1, 2011 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 111 µg/L, federal limit 80 µg/L (1.4 times the limit)
Jan 1, 2011 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 115 µg/L, federal limit 80 µg/L (1.4 times the limit)
Oct 1, 2010 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 134 µg/L, federal limit 80 µg/L (1.7 times the limit)
Jul 1, 2010 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 130 µg/L, federal limit 80 µg/L (1.6 times the limit)
Apr 1, 2010 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 121 µg/L, federal limit 80 µg/L (1.5 times the limit)
Jan 1, 2010 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 122 µg/L, federal limit 80 µg/L (1.5 times the limit)
Oct 1, 2009 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 120 µg/L, federal limit 80 µg/L (1.5 times the limit)
Jul 1, 2009 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 119 µg/L, federal limit 80 µg/L (1.5 times the limit)
Apr 1, 2009 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Jan 1, 2009 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Oct 1, 2008 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 61 µg/L, federal limit 60 µg/L (at or just above the limit)
Jul 1, 2008 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 128 µg/L, federal limit 80 µg/L (1.6 times the limit)
Jul 1, 2008 Resolved
Haloacetic Acids (HAA5)
Contaminant limit exceeded
Measured 61 µg/L, federal limit 60 µg/L (at or just above the limit)
Apr 1, 2008 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Measured 128 µg/L, federal limit 80 µg/L (1.6 times the limit)
Apr 1, 2008 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Jan 1, 2008 Resolved
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Apr 1, 2007 Archived
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Jan 1, 2007 Archived
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Oct 1, 2006 Archived
Total Trihalomethanes (TTHMs)
Contaminant limit exceeded
Jul 1, 2006 Archived
CARBON, TOTAL
Treatment technique failure
Jan 1, 2006 Archived
Stage 1 Disinfection Byproducts Rule
Treatment technique failure
Oct 1, 2003 Resolved
Surface Water Treatment Rule
Treatment technique failure
Feb 1, 1998 Archived
Surface Water Treatment Rule
Treatment technique failure
Feb 1, 1996 Archived
Surface Water Treatment Rule
Treatment technique failure
Jul 1, 1995 Archived
Surface Water Treatment Rule
Treatment technique failure
Apr 1, 1995 Archived
Surface Water Treatment Rule
Treatment technique failure
Mar 1, 1995 Archived
Surface Water Treatment Rule
Treatment technique failure
Apr 1, 1994 Archived
Surface Water Treatment Rule
Treatment technique failure
Jan 1, 1994 Archived

Enforcement actions

Arkansas regulators took 4 formal enforcement actions against Waldron Waterworks between 1995 and 2009. The most recent was a consent decree or court judgment in August 2009.

Date By Action Violations covered
Aug 13, 2009 Arkansas Consent decree or court judgment 17 violations (17 health-based): Stage 1 Disinfection Byproducts Rule, Total Trihalomethanes (TTHMs), Haloacetic Acids (HAA5), CARBON, TOTAL
May 31, 2007 Arkansas Compliance order (no penalty) 6 violations (6 health-based): Total Trihalomethanes (TTHMs), Stage 1 Disinfection Byproducts Rule, CARBON, TOTAL
Sep 27, 1995 Arkansas Compliance order (no penalty) 3 violations (3 health-based): Surface Water Treatment Rule
Sep 26, 1995 Arkansas Compliance order (no penalty) 4 violations (3 health-based): Total Coliform, Surface Water Treatment Rule

What the violations mean

Stage 1 Disinfection Byproducts Rule

1 incident

The system did not meet a treatment requirement of the Stage 1 Disinfectants and Disinfection Byproducts Rule

Byproducts form when disinfectants react with natural material in water. Long-term exposure above federal limits may increase cancer risk

Where the water comes from

Waldron Waterworks draws water from 2 surface water intakes.

Annual water quality report

Waldron Waterworks must give its customers an annual water quality report (Consumer Confidence Report) by July 1, with the levels its tests found in the previous year.

Where the state allows it, systems serving fewer than 10,000 people may publish the report in a local newspaper or news site instead of mailing it, and must provide a copy on request.

Find a posted report with EPA's Consumer Confidence Report search

Testing your own water

To test the water at your tap, or a private well this record does not cover, use a laboratory certified for drinking water by Arkansas.